Data from analogue inputs
Data from analogue inputs
Feature
Value
Description
Cable length
max. 30 m
Applies to unshielded connection cables.
Cables over 30 m in length must be shielded.
Modulation method
Delta-sigma modula-
tion
–
Shared points be-
tween the channels
AGND reference
–
Clamp arrangement
Shielding on common
AGND pins
–
Sampling dura-
tion/rate for measur-
ing values
1 ms
A reading is taken from each input channel
every millisecond regardless of how many
channels are actually in operation
Sampling rate
AI-PT operating
mode
250 ms
In AI-PT operating mode, calculations are car-
ried out according to the millisecond sampling
rate. A new value is available in the user pro-
gram every 250 ms.
Digital filtering
Possible
filter settings
Time range for averaging
Time range for averaging
AI-PT operating mode
0
1 ms
0.25 s
10
10 ms
2.5 s
100
100 ms
25 s
1,000
1,000 ms (1 s)
250 s
If filtering is active, an average is calculated for the set time range. However, a value is still issued dur-
ing the sampling rate interval. For example, if the filter is set to 1,000, the average of the measure-
ments for the last 1,000 ms / 1,000 measurements is issued each millisecond (or, in the case of AI-PT
operating mode, every 250 ms, the average from the last 250 ms / 1,000 measurements).
The filtering can be activated and configured using CODESYS V3. The sampling rate is constant. It can
only be filtered with a whole multiple of the sampling rate.