Voltage input AI (U)
Fig. 18: Connection example: voltage input
Only use the corresponding AGND for each voltage input.
Do not connect AGNDs from different channels.
AGNDs from different channels must always be connected separately to plug X1.
Do not connect to the common GND. The required connections can already be found on the cir-
cuit board.
Cables to the analogue sensors/encoders should be connected as directly as possible (avoid the
use of terminals and terminal blocks).