Data from the digital outputs
Feature
Value
Description
Type of output
Semiconductor
Non-storing, current supplying (positive
switching)
Protective circuit for
inductive loads
41 V clamping volt-
age (typ.) compared
to +24 V
Fast de-excitation (must be provided exter-
nally)
Status display
Yes
One orange LED per output
Lights up at logical 1
Overload protection
Yes
In the case of thermal overload, auto-resetting
Short-circuit protec-
tion response
threshold
Yes
Electronic current limitation: typ. 7 A
The current is limited electronically. Activation
of the short-circuit protection results in thermal
overload and tripping of the thermal overload
protection.
Permissible limit values starting from cold
state: max. 10,000 short circuits, total duration
max. 500 hours.
Status in unsafe op-
erating conditions
Logical 0
If the supply voltage is insufficient and the
control system is started up or shut down, the
outputs are set to logical 0.
Output delay “0” af-
ter “1”
typ. 1 ms
–
Output delay “1” af-
ter “0”
typ. 1 ms
–
Output capacitance
< 20 nF
–
Rated voltage
+24 V DC
–
Voltage drop (at
rated current)
< 0.1 V
–
Rated current at “1”
signal
0.5 A
–
Total current of all
outputs
max. 2 A
–
Parallel switching of
two outputs
max. 1 A
Maximum permissible value with a logical
connection to increase power