6

EXCLUSIVE GREEN C.S.I. - R.S.I.

INSTALLATION “SEALED” (TYPE C)

Boiler is a C-type appliance (sealed chamber) and must be safely connected to
fume exhaustion duct and burning air suction duct, both getting outside;
appliance cannot operate without these ducts.

Concentric outlets (Ø 60-100) (Fig. 1.14)

Concentric ducts may be placed in the most suitable direction for installation
requirements but special care must be taken as regards the external tempera-
ture and the length of the duct.

Rectilinear length means without bends, outlet ends and connections.
The fumes outlet duct must slope by 1% towards the condensate collector.
Uninsulated fumes outlets are potential hazards.
The boiler automatically adapts ventilation according to the type of
installation and the length of the duct.
Do not obstruct or narrow the comburent air inlet duct in any way.

To install follow the instructions supplied with the kit.

Max length fumes

outlet duct Ø 80 mm

48 m
48 m
60 m

Pressure drop for each

bend (45°/90°) [m]

0,5 / 0,8

16 R.S.I.

25 C.S.I.-R.S.I.
35 C.S.I.-R.S.I.

Max linear length concentric

duct Ø 60-100 mm

7,80 m
7,80 m
7,80 m

Pressure drop for each

bend (45°/90°) [m]

0,5 / 0,8

16 R.S.I.

25 C.S.I.-R.S.I.
35 C.S.I.-R.S.I.

Horizontal

Max linear length concentric

duct Ø 60-100 mm

8,80 m
8,80 m
8,80 m

Pressure drop for each

bend (45°/90°) [m]

0,5 / 0,8

16 R.S.I.

25 C.S.I.-R.S.I.
35 C.S.I.-R.S.I.

Vertical

Max linear length concentric

duct Ø 80-125 mm

17 m
17 m
28 m

Pressure drop for each

bend (45°/90°) [m]

0,5 / 0,9

16 R.S.I.

25 C.S.I.-R.S.I.
35 C.S.I.-R.S.I.

Twin outlets (Ø 80) (Fig. 1.15)

The split duct can be aimed in the most suitable direction for installation needs.
The combustion-supporting air intake duct must be connected to the entrance
after having removed the closing cap, attached with three screws, and having
attached a suitable adaptor.
The fumes outlet duct must be connected to the fumes outlet after having
installed a suitable adaptor.
For the installation process, follow the instructions supplied with the kit for the
specific accessory for condensation boilers.

The fumes outlet duct must slope by 1% towards the condensate collector.
The boiler automatically adapts ventilation according to the type of instal-
lation and the length of the duct. Do not obstruct or narrow the comburent
air inlet duct in any way.
For an indication of the maximum lengths of every single pipe, refer to the
graphs (Fig. 1.16).
Using longer ducts causes a loss in the power of the boiler.

Max length

twin duct Ø 80 mm

40 + 40 m
40 + 40 m
50 + 50 m

Pressure drop for each

bend (45°/90°) [m]

0,5 / 0,8

16 R.S.I.

25 C.S.I.-R.S.I.
35 C.S.I.-R.S.I.

Rectilinear length means without bends, outlet ends and connections.

Suggestions to correctly eliminate air from the heating system and
boiler (Fig. 8.2)

We recommend carrying out the sequence of operations given below during
first installation or with extraordinary maintenance work:
1. Using a CH11 spanner open the manual air vent valve located above the air

box; the tube supplied with the boiler must be connected to the valve to let
out the water into an outside container.

2. Open the manual system filling stopcock on the water group, wait until the

water starts coming out of the valve;

3. Switch on the boiler leaving the gas cock closed;
4. Use the room thermostat or the remote control panel to activate request for

heat so that the three-way will turn to heating;

5. Turn on a tap to activate request for hot water (for instantaneous boilers

only; use the water heater thermostat for boilers just for heating connected
to an external water heater) for an interval of 30” every minute to make the
three-way cycle from heating to hot water and vice versa about ten times
(the boiler will be go into alarm as there is no gas under these circumstances,
it must therefore be reset every time this happens);

6. Continue the sequence until water only comes out of the manual air vent

valve and the flow of air has finished; close the manual air vent valve at this
point;

7. Make sure the system is at the correct pressure (1 bar is ideal);
8. Close the manual system filling stopcock on the water group;
9. Open the gas cock and ignite the boiler.

9 - FUMES EXHAUSTION AND BURNING AIR SUCTION

EXHAUSTION CONFIGURATIONS (Fig. 1.11-1.12)

Boiler is homologated for the following exhaustion configurations:

B23P-B53P -

 Suction in room and discharge outside

C13 -

 Concentric wall exhaustion. Pipes can separately start from boiler, but

outlets must be concentric or close enough to be subject to similar wind
conditions (within 50 cm)

C23 -

 Concentric exhaustion in common chimney (suction and exhaustion in

the same chimney)

C33 -

 Concentric roof exhaustion. Outlets like C13

C43 -

 Exhaustion and suction in common separate chimneys, but subject to

similar wind conditions

C53 -

 Wall or roof separate exhaustion and suction in different pressure areas.

Exhaustion and suction must never be located on opposite walls

C63 -

 Exhaustion and suction with separately certified and sold pipes (1856/1)

C83 -

 Single or common chimney exhaustion and wall suction

Refer to regulations in force for exhaustion of combustion products.
Boiler is provided for without fume exhaustion/air suction kit, since forced draught
sealed chamber accessories can be used, as they better adapt to installation
characteristics.
For fume extraction and burning air restoration in boiler, use original pipes or
other EC-certified pipes with equivalent characteristics; check connection is
correct as shown on instructions fume accessories provided for with. More
appliances can be connected to a single chimney, provided that all appliances
are sealed chamber type.

“FORCED OPEN” INSTALLATION (TYPE B23P-B53P, intake inside and
outlet outside) - Fumes outlet duct Ø 80 mm (Fig. 1.13)

The fumes outlet duct can be aimed in the most suitable direction for installation
needs. To install follow the instructions supplied with the kit.

In this configuration, the boiler is connected to the Ø 80 mm fumes outlet
duct by means of a Ø 60-80 mm adaptor.
In this case, the combustion supporting air is taken from the room in which
the boiler is installed, which must be a suitable and ventilated technical
room.
Non-insulated fumes outlet ducts are potential sources of danger.
Provision must be made for a 1% slope of the fumes outlet duct towards
the boiler.

Concentric outlets (Ø 80-125) (Fig. 1.14)

For this installation it is necessary to install the suitable adaptor kit. Ducts may
be placed in the most suitable direction for installation requirements. For the
installation process, follow the instructions supplied with the kit for the specific
accessory for condensation boilers.

Summary of Contents for EXCLUSIVE GREEN CSI 16

Page 1: ...C S I R S I EN INSTALLER AND USER MANUAL ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO HU TELEP T I S FELHASZN L I K ZIK NYV RO MANUAL DE INSTALARE SI UTILIZARE DK INSTALLATIONS OG BR...

Page 2: ...E jelet RO Centrala EXCLUSIVE GREEN este fabricata in conformitate cu cerintele urmatoarelor Directive Directiva gaz 90 396 EEC Directiva eficienta 92 42 EEC Directiva compatibilitate electromagnetica...

Page 3: ...s o aqueles referidos quer ao usu rio quer ao instalador Os modelos GREEN C S I e GREEN R S I t m os pain is de comando diferentes veja se o desenho Sugerimos consultar o manual para as instru es rel...

Page 4: ...m switch before cleaning it is forbidden to modify the safety or adjustment devices without the manufacturer s permission and relative instructions do not pull detach or twist the wires from the boile...

Page 5: ...and remove the shell Fig 1 2 lift up the panel and turn it forwards open the terminal board covers making them slide in the direction of the arrows Fig 1 8 E high voltage connections 230 V F low volt...

Page 6: ...leaving the gas cock closed 4 Use the room thermostat or the remote control panel to activate request for heat so that the three way will turn to heating 5 Turn on a tap to activate request for hot w...

Page 7: ...r s mm m m mm mm m mm m m mm m m class p p m p p m C p p m p p m C 25 21500 24 43 21006 26 13 22468 6 5160 5 86 5041 6 44 5537 25 21500 25 21500 6 5160 6 5160 97 7 97 7 101 2 97 9 104 5 107 3 107 1 13...

Page 8: ...s diaphragm Burner length CH maximum gas capacity CH minimum gas capacity Numbers of fan revolutions at slow start Maximum number of fan revolutions Minimum number of fan revolutions EXCLUSIVE GREEN R...

Page 9: ...the winter comfort mode If it was in the OFF mode the display will show two segments in the central area Fig 3 Press the button to enable operation press the function selector until the indicator mov...

Page 10: ...10 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 5 6 7 B 8 9 10 Tap closed 11 12 13...

Page 11: ...Fig 8 The boiler will remain working until the set temperatures are reached after which it will go on stand by In the event of ignition or operating faults the boiler will perform a safety stop The f...

Page 12: ...n reference to the second circuit only if it is connected S A R A function Fig 21 If the winter mode is selected the S A R A AutomaticAmbientAdjustment System function can be activated Turn the heatin...

Page 13: ...er only if water tank connected Info button shows a sequence of information concerning the operating status of the machine Switching on Switch on the boiler as follows access the gas tap through the s...

Page 14: ...14 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 5 6 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 7 9 D 11 10 8...

Page 15: ...heating water tank with sensor to adjust domestic hot water temperature storaged in the water tank turn switch D Fig 9 clocwise to increase and anticlockwise to decrease The bar segments light up ever...

Page 16: ...the word InFO Fig 17 Info 1 only with the external probe connected displays external temperature e g 12 C Fig 18 The values shown on the display range between 30 C and 35 C Beyond these values the dis...

Page 17: ...ls and appear either together or separately For a description of the faults consult the following table D Permanent T Temporary In this operating status the boiler attempts to eliminate the fault on i...

Page 18: ...select functions button and the button together for about 10 seconds The display will look like Fig F Enter the password for accessing the parameter modifications function by turning the domestic hot...

Page 19: ...FREEZE FUNCTION TEMPERATURE ON HEATING ANTIFREEZE FUNC DELIVERY TEMP ON THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY EXTERNAL SENSOR REACTIVITY SEMI AUTOMATIC FILLING AUTOMATIC FILLING PRESS...

Page 20: ...delivery temperature but affect the calculation made to automatically determine its value by modifying the reference tempera ture of the system 0 20 C For boilers fitted with the S A R A BOOSTER funct...

Page 21: ...n by turning the domestic hot water temperature selector to the required value The password is located on the back side of the control panel Confirm by pressing ENTER Calibration phases Turn the domes...

Page 22: ...ave set by pressing ENTER MAXIMUM POWER ADJUSTMENT P HH Fig 1 17 Turn the boiler OFF Select the parameter HH and wait for the boiler to come on Check that the maximum CO2 reading on the analyser see p...

Page 23: ...obes in the designated positions on the air chamber after having removed screw B and cap C Fig 1 20 make sure in the HH and LL parameters that the CO2 values correspond with those indicated in the tab...

Page 24: ...120 EXCLUSIVE GREEN C S I R S I...

Page 25: ...21 Br nder 22 Hoved veksler 23 Bl ser 24 Mixer 25 Gas dyse 26 Ekspansionsbeholder 27 Manometer 28 Ikke DK 29 Ikke DK 30 Gas armatur 31 Kondensafl b EN BOILER OPERATING ELEMENTS 1 Filling tap C S I 2...

Page 26: ...tr s vias I Bomba circuladora J V lvula de sangria ar inferior K Tanque de expans o L Sonda NTC retorno M Permutador circuito prim rio N V lvula de sangria ar superior O Sonda NTC sa da P Transdutor d...

Page 27: ...e de expans o P Sonda NTC retorno Q Permutador circuito prim rio R V lvula de sangria ar superior S Sonda NTC sa da T Transdutor de press o U Hidr metro V Boiler pode se fornecer a pedido HU V ZKERING...

Page 28: ...4 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN C S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Page 29: ...5 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN R S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Page 30: ...1 Transformador principal TRX Transformador para ventilador TSC2 Transformador de encendido V Ventilador PT DIAGRAMA EL CTRICO MULTIFILAR SUGERE SE A POLARIZA O L N Blu Azul Marrone Castanha Nero Pret...

Page 31: ...circuit apa calda menajera NTC C S I T BOLL Termostat rezervor apa R S I T F Termostat de fum T L A Termostat limita pentru supra temperatura apei T P Traductor de presiune TR1 Transformator principal...

Page 32: ...28 EXCLUSIVE GREEN C S I R S I a b c f GREEN C S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN R S I d e g GREEN C S I GREEN R S I 2 1 1 2 1 3 4 5 6 4 5 1 7 10 P2 8 9...

Page 33: ...l circulador suplementario en la regleta de 2 polos en la zona dimensionada para V 230 Voltios La caldera es capaz de gestionar un circulador suplementario conectado hidr ulicamente como se muestra en...

Page 34: ...u functiile de voltaj redus la bornele corespunzatoare cu 10 poli de la nivelul tabloului de conexiune M10 dupa cum este indicat Montati P O S DHW ceas de control conform figurii dupa de ati indeparta...

Page 35: ...e que a caldeira funciona correctamente se no permutador do aquecimento houver uma circula o de gua suficiente Para esta finalidade a caldeira dotada de um by pass autom tico que prov quaisquer que se...

Page 36: ...en RO dimensiuni in mm DK m lt i mm A EN A condensate outlet C water gas ES A descarga condensado C agua gas PT A descarga condensado C gua g s HU A kondenzv z elvezet s C v z g z RO A scurgere apa de...

Page 37: ...133 EXCLUSIVE GREEN C S I R S I C S I E F E F G R S I 1 8 G B F C A D A D F G E 1 9 C S I R S I 1 6 1 7 A...

Page 38: ...IRA O AR HU KONCENTRIKUS F STG ZELVEZET S LEVEG BESZ V S RO TUBULATURA CONCENTRICA ADMISIE EVACUARE DK BALANCERET AFTR K AFKAST LUFTINDTAG EN SPLIT DUCTS FOR FUMES OUTLET AIR INTAKE ES CONDUCTO DESDOB...

Page 39: ...0 180 190 200 B 25 C S I R S I A 0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70 80 90 100 35 C S I R S I B A 0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120 130 1 16 1 17 A B EN A...

Page 40: ...Via Risorgimento 13 23900 Lecco LC ITALY Cod 20001690 06 08 Ed 1...

Reviews: