20

EXCLUSIVE GREEN C.S.I. - R.S.I.

To access the programming mode, consult “Programming parameters”.

PARAMETER 03. Type of building

In order to calculate delivery temperature, the temperature control system does
not directly use the external temperature value but considers the heat insulation
of the building: in well-lagged buildings, external temperature variations affect
the ambient temperature less than they do in badly-lagged buildings. Use
parameter 3 to set the heat insulation level of the building according to the
following scheme:

PARAMETERS 21 and 22. Maximum and minimum delivery
temperature

These two parameters limit the delivery temperature automatically produced by
the TEMPERATURE CONTROL function. PARAMETER 21 determines
MAXIMUM DELIVERY TEMPERATURE (MAXIMUM HEATING SET POINT)
while PARAMETER 22 determines MINIMUM DELIVERY TEMPERATURE
(MINIMUM HEATING SET POINT).

PARAMETER 44. Enable thermoregulation function

The connected external temperature probe combined with PARAMETER 44
provides the following operating modes:
EXTERNAL PROBE CONNECTED and PARAMETER 44 = 0 (OFF) in this
case the TEMPERATURE CONTROL function is disabled even though the
external probe is connected. The temperature read by the external probe can
always be viewed by pressing the INFO button. The TEMPERATURE
CONTROL symbols are not displayed.
EXTERNAL PROBE CONNECTED, PARAMETER 44 = 1 (ON) in this case
the TEMPERATURE CONTROL function is enabled. The temperature read by
the external probe and the TEMPERATURE CONTROL symbols can be viewed
by pressing the INFO button.

The TEMPERATURE CONTROL function cannot be enabled unless the
external probe has been fitted and connected. In this case, PARAMETER
44 is ignored and has no effect on boiler operation.

PARAMETER 45. Choosing the offset temperature curve (graph 1)

The offset heating curve maintains a theoretical ambient temperature of 20°C
at external temperatures ranging from +20°C to -20°C. The choice of the curve
depends on the rated minimum external temperature (on the geographical area,
therefore) and the rated delivery temperature (on the type of system, therefore)
and must be carefully calculated by the fitter using the following formula:

If, from your calculations, you obtain an intermediate value between two curves,
we suggest choosing the compensation curve closest to the value obtained.
Example: if the value obtained from the calculations is 8, this is between curve
7.5 and curve 10. In this case, choose the closest curve, which is 7.5.

PARAMETER 51. Type of heat request
IF AN AMBIENT THERMOSTAT IS CONNECTED TO THE BOILER, SET
PARAMETER 51 = 0 (graph 2).

The ambient thermostat makes a heat request when its contact closes, while it
stops it when its contact opens. Though delivery temperature is automatically
calculated by the boiler, the user may manually override it. By modifying
HEATING on the user interface, the HEATING SET POINT will no longer be
available but just a value that can be set from +5 to -5°C as required. Modifications
to this value do not directly change delivery temperature but affect the calculation
made to automatically determine its value by modifying the reference tempera-
ture of the system (0 = 20°C).
For boilers fitted with the S.A.R.A. BOOSTER function, if the AMBIENT
THERMOSTAT remains closed for a long time, the boiler automatically increases
the delivery temperature which is added to the effect of the temperature control
function. When the AMBIENT THERMOSTAT opens, the boiler automatically
returns to the value determined by the TEMPERATURE CONTROL function.

IF A PROGRAMMABLE TIMER IS CONNECTED TO THE BOILER, SET
PARAMETER 51 = 1 (graph 3).

When the contact is closed, the heat request is made by the delivery probe on
the basis of the external temperature in order to maintain the rated ambient
temperature at the DAY level (20°C). When the contact opens, it does not stop
the heat request but reduces (parallel shift) the temperature curve to the NIGHT
level (16°C). Though delivery temperature is automatically calculated by the
boiler, the user may manually override it.
By modifying HEATING on the user interface, the HEATING SET POINT will
no longer be available but just a value that can be set from +5 to –5°C as
required.
Modifications to this value do not directly change delivery temperature but affect
the calculation made to automatically determine its value by modifying the
reference temperature of the system (0 = 20°C for DAY level; 16°C for NIGHT
level).

CONNECT AT/BT

In case of using CONNECT AT/BT, accessory supplied on request, the boiler
gives the possibility to choose 2 thermoregulation curves:
- OTC 1 CH (parameter 45) for a direct system
- OTC 2 CH (parameter 47) for a mixed system.
Even in case of second circuit (2CH) the curve depends on the external minimum
project temperature (on the geographical area, therefore) and on the delivey
project temperature (on the type of system, therefore); the installer must to put
attention to calculate it using the following formula:

3

21
22
44
45
51

PARAMETER

TYPE OF BUILDING
MAXIMUM HEATING SET POINT
MINIMUM HEATING SET POINT
ENABLE THERMOREGULATION FUNCTION
OFFSET TEMPERATURE CURVE
TYPE OF HEAT REQUEST

AVAILABLE IN THE PROGRAMMING MODE

INSTALLATION AND CALIBRATION & SERVICE
INSTALLATION
INSTALLATION
INSTALLATION
INSTALLATION AND CALIBRATION & SERVICE
INSTALLATION

New

houses

A
B
C
D

Old

houses

19
20
19
18

Hollow

bricks

14
16
15
12

Solid

bricks

12
15
14
10

Stones

8

11

9
5

16 - SETTING THE THERMOREGULATION

Checking the connection with the external probe

After connecting the external probe to the boiler, use the INFO function to check that the probe has been automatically recognised by the temperature control card.
Immediately after installation, the value read by the probe may very well be higher then that measured by a reference probe.
Enable and optimise the THERMOREGULATION function by setting the following parameters:

Type of building

D

C

B

A

rated delivery T - 20

P. 45 = 10 x

20- rated min. external T

rated delivery T - 20

P. 47 = 10 x

20- rated min. external T

Parameters 31 and 32 give the possibility to define the maximum and the
minimum central heating set-point of the second circuit.
To correct the curve in this configuration, please refer to the instructions supplied
with the accessory.

Summary of Contents for EXCLUSIVE GREEN CSI 16

Page 1: ...C S I R S I EN INSTALLER AND USER MANUAL ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO HU TELEP T I S FELHASZN L I K ZIK NYV RO MANUAL DE INSTALARE SI UTILIZARE DK INSTALLATIONS OG BR...

Page 2: ...E jelet RO Centrala EXCLUSIVE GREEN este fabricata in conformitate cu cerintele urmatoarelor Directive Directiva gaz 90 396 EEC Directiva eficienta 92 42 EEC Directiva compatibilitate electromagnetica...

Page 3: ...s o aqueles referidos quer ao usu rio quer ao instalador Os modelos GREEN C S I e GREEN R S I t m os pain is de comando diferentes veja se o desenho Sugerimos consultar o manual para as instru es rel...

Page 4: ...m switch before cleaning it is forbidden to modify the safety or adjustment devices without the manufacturer s permission and relative instructions do not pull detach or twist the wires from the boile...

Page 5: ...and remove the shell Fig 1 2 lift up the panel and turn it forwards open the terminal board covers making them slide in the direction of the arrows Fig 1 8 E high voltage connections 230 V F low volt...

Page 6: ...leaving the gas cock closed 4 Use the room thermostat or the remote control panel to activate request for heat so that the three way will turn to heating 5 Turn on a tap to activate request for hot w...

Page 7: ...r s mm m m mm mm m mm m m mm m m class p p m p p m C p p m p p m C 25 21500 24 43 21006 26 13 22468 6 5160 5 86 5041 6 44 5537 25 21500 25 21500 6 5160 6 5160 97 7 97 7 101 2 97 9 104 5 107 3 107 1 13...

Page 8: ...s diaphragm Burner length CH maximum gas capacity CH minimum gas capacity Numbers of fan revolutions at slow start Maximum number of fan revolutions Minimum number of fan revolutions EXCLUSIVE GREEN R...

Page 9: ...the winter comfort mode If it was in the OFF mode the display will show two segments in the central area Fig 3 Press the button to enable operation press the function selector until the indicator mov...

Page 10: ...10 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 5 6 7 B 8 9 10 Tap closed 11 12 13...

Page 11: ...Fig 8 The boiler will remain working until the set temperatures are reached after which it will go on stand by In the event of ignition or operating faults the boiler will perform a safety stop The f...

Page 12: ...n reference to the second circuit only if it is connected S A R A function Fig 21 If the winter mode is selected the S A R A AutomaticAmbientAdjustment System function can be activated Turn the heatin...

Page 13: ...er only if water tank connected Info button shows a sequence of information concerning the operating status of the machine Switching on Switch on the boiler as follows access the gas tap through the s...

Page 14: ...14 EXCLUSIVE GREEN C S I R S I Open position 1 2 3 4 5 6 A 4 5 C 3 C 2 C 1 C 0 C 1 C 2 C 3 C 4 5 C 7 9 D 11 10 8...

Page 15: ...heating water tank with sensor to adjust domestic hot water temperature storaged in the water tank turn switch D Fig 9 clocwise to increase and anticlockwise to decrease The bar segments light up ever...

Page 16: ...the word InFO Fig 17 Info 1 only with the external probe connected displays external temperature e g 12 C Fig 18 The values shown on the display range between 30 C and 35 C Beyond these values the dis...

Page 17: ...ls and appear either together or separately For a description of the faults consult the following table D Permanent T Temporary In this operating status the boiler attempts to eliminate the fault on i...

Page 18: ...select functions button and the button together for about 10 seconds The display will look like Fig F Enter the password for accessing the parameter modifications function by turning the domestic hot...

Page 19: ...FREEZE FUNCTION TEMPERATURE ON HEATING ANTIFREEZE FUNC DELIVERY TEMP ON THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY EXTERNAL SENSOR REACTIVITY SEMI AUTOMATIC FILLING AUTOMATIC FILLING PRESS...

Page 20: ...delivery temperature but affect the calculation made to automatically determine its value by modifying the reference tempera ture of the system 0 20 C For boilers fitted with the S A R A BOOSTER funct...

Page 21: ...n by turning the domestic hot water temperature selector to the required value The password is located on the back side of the control panel Confirm by pressing ENTER Calibration phases Turn the domes...

Page 22: ...ave set by pressing ENTER MAXIMUM POWER ADJUSTMENT P HH Fig 1 17 Turn the boiler OFF Select the parameter HH and wait for the boiler to come on Check that the maximum CO2 reading on the analyser see p...

Page 23: ...obes in the designated positions on the air chamber after having removed screw B and cap C Fig 1 20 make sure in the HH and LL parameters that the CO2 values correspond with those indicated in the tab...

Page 24: ...120 EXCLUSIVE GREEN C S I R S I...

Page 25: ...21 Br nder 22 Hoved veksler 23 Bl ser 24 Mixer 25 Gas dyse 26 Ekspansionsbeholder 27 Manometer 28 Ikke DK 29 Ikke DK 30 Gas armatur 31 Kondensafl b EN BOILER OPERATING ELEMENTS 1 Filling tap C S I 2...

Page 26: ...tr s vias I Bomba circuladora J V lvula de sangria ar inferior K Tanque de expans o L Sonda NTC retorno M Permutador circuito prim rio N V lvula de sangria ar superior O Sonda NTC sa da P Transdutor d...

Page 27: ...e de expans o P Sonda NTC retorno Q Permutador circuito prim rio R V lvula de sangria ar superior S Sonda NTC sa da T Transdutor de press o U Hidr metro V Boiler pode se fornecer a pedido HU V ZKERING...

Page 28: ...4 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN C S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Page 29: ...5 EXCLUSIVE GREEN C S I R S I EXCLUSIVE GREEN R S I EN MULTI WIRE DIAGRAM ES ESQUEMA EL CTRICO MULTIHILO PT DIAGRAMA EL CTRICO MULTIFILAR HU KAPCSOL SI RAJZ RO SCHEMA ELECTRICA MULTIFILARA DK EL DIAGR...

Page 30: ...1 Transformador principal TRX Transformador para ventilador TSC2 Transformador de encendido V Ventilador PT DIAGRAMA EL CTRICO MULTIFILAR SUGERE SE A POLARIZA O L N Blu Azul Marrone Castanha Nero Pret...

Page 31: ...circuit apa calda menajera NTC C S I T BOLL Termostat rezervor apa R S I T F Termostat de fum T L A Termostat limita pentru supra temperatura apei T P Traductor de presiune TR1 Transformator principal...

Page 32: ...28 EXCLUSIVE GREEN C S I R S I a b c f GREEN C S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN C S I GREEN R S I GREEN R S I d e g GREEN C S I GREEN R S I 2 1 1 2 1 3 4 5 6 4 5 1 7 10 P2 8 9...

Page 33: ...l circulador suplementario en la regleta de 2 polos en la zona dimensionada para V 230 Voltios La caldera es capaz de gestionar un circulador suplementario conectado hidr ulicamente como se muestra en...

Page 34: ...u functiile de voltaj redus la bornele corespunzatoare cu 10 poli de la nivelul tabloului de conexiune M10 dupa cum este indicat Montati P O S DHW ceas de control conform figurii dupa de ati indeparta...

Page 35: ...e que a caldeira funciona correctamente se no permutador do aquecimento houver uma circula o de gua suficiente Para esta finalidade a caldeira dotada de um by pass autom tico que prov quaisquer que se...

Page 36: ...en RO dimensiuni in mm DK m lt i mm A EN A condensate outlet C water gas ES A descarga condensado C agua gas PT A descarga condensado C gua g s HU A kondenzv z elvezet s C v z g z RO A scurgere apa de...

Page 37: ...133 EXCLUSIVE GREEN C S I R S I C S I E F E F G R S I 1 8 G B F C A D A D F G E 1 9 C S I R S I 1 6 1 7 A...

Page 38: ...IRA O AR HU KONCENTRIKUS F STG ZELVEZET S LEVEG BESZ V S RO TUBULATURA CONCENTRICA ADMISIE EVACUARE DK BALANCERET AFTR K AFKAST LUFTINDTAG EN SPLIT DUCTS FOR FUMES OUTLET AIR INTAKE ES CONDUCTO DESDOB...

Page 39: ...0 180 190 200 B 25 C S I R S I A 0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70 80 90 100 35 C S I R S I B A 0 10 20 30 40 50 60 70 80 90 0 10 20 30 40 50 60 70 80 90 100 110 120 130 1 16 1 17 A B EN A...

Page 40: ...Via Risorgimento 13 23900 Lecco LC ITALY Cod 20001690 06 08 Ed 1...

Reviews: