Refer to regulations in force for exhaustion of combustion products.

Boiler is provided for without fume exhaustion/air suction kit, since 

forced draught sealed chamber accessories can be used, as they 

better adapt to installation characteristics.

For fume extraction and burning air restoration in boiler, use original 

pipes or other EC-certi

fi

 ed pipes with equivalent characteristics; 

check connection is correct as shown on instructions fume accesso-

ries provided for with. More appliances can be connected to a single 

chimney, provided that all appliances are sealed chamber type.

Boiler is a C-type appliance (sealed chamber) and must be safely 

connected to fume exhaustion duct and burning air suction duct, 

both getting outside; appliance cannot operate without these ducts.

Concentric outlets (ø 60-100)

Concentric ducts may be placed in the most suitable direction for 

installation requirements but special care must be taken as regards 

the external temperature and the length of the duct.

Consult the graphs to 

fi

 nd out whether a condensate collector is 

required.

8

FUMES EXHAUSTION AND BURNING 

AIR SUCTION (MIX C.S.I. - MIX R.S.I.)

 

If the appliance works at temperatures lower than 50 °C (e.g.: 

with external probe), the maximum permitted length must be 

decreased by 1 metre.

 

The fumes outlet duct must slope by 1% towards the condensate 

collector.

 

The condensate collector can only be applied to the fumes 

outlet, within 0.85 m from the boiler; connect the trap of the 

condensate collector to a waste water drain.

 

Uninsulated fumes outlets are potential hazards.

 

The boiler automatically adapts ventilation according to the 

type of installation and the length of the duct. Do not obstruct 

or narrow the comburent air inlet duct in any way.

EXHAUSTION CONFIGURATIONS (

fi

 g. 7)

Boiler is homologated for the following exhaustion con

fi

 gurations:

C12-C12x

  Concentric wall exhaustion. Pipes can separately start 

from boiler, but outlets must be concentric or close enough 

to be subject to similar wind conditions (within 50 cm) 

C22

   

Concentric exhaustion in common chimney (suction and 

exhaustion in the same chimney)

C32-C32x

  Concentric roof exhaustion. Outlets like C12

C42-C42x

  Exhaustion and suction in common separate chimneys, 

but subject to similar wind conditions

C52-C52x

  Wall or roof separate exhaustion and suction in different 

pressure areas. Exhaustion and suction must never be 

located on opposite walls

C62-C62x

  Exhaustion and suction with separately certi

fi

 ed and sold 

pipes (1856/1)

C82-C82x

  Single or common chimney exhaustion and wall suction.

Maximum length concentric ducts ø 60-100 26 MIX C.S.I.

EXHAUSTION LENGHT (m)

EXTERNAL TEMPERATURE (°C)

Maximum length concentric ducts ø 60-100 

30 MIX C.S.I. - 30 MIX R.S.I.

Maximum length concentric ducts ø 60-100

 35 MIX C.S.I. - 35 MIX R.S.I.

EXHAUSTION LENGHT (m)

EXHAUSTION LENGHT (m)

EXTERNAL TEMPERATURE (°C)

EXTERNAL TEMPERATURE (°C)

Fig. 9

Concentric outlets (ø 80-125)

The boiler is furnished predisposed for connection to concentric dis-

charge/aspiration ducts and with the air aspiration aperture closed.

The concentric pipes may be oriented in the direction best suited to 

the requirements of the premises, respecting the maximum lengths 

indicated in the table below.

For installation, follow the instructions provided with the kit.

CONCENTRIC OUTLETS (ø 60-100)

Fig. 8a

Concentric 

outlet

Clamp

Condensate 

collector

Condensate 

drain trap

Execute a Ø 140 mm hole for transit through the wall.

Particular care is required with the external temperature and the 

length of the pipe. Refer to the graphics to establish whether the 

condensation trap is mandatory or not. In the case of operation at 

water temperatures below 60 °C, the use of a condensation trap 

is mandatory. In the case of use of condensation trap the fumes 

discharge pipe must be inclined by 1% towards the trap.

Connect the condensation trap siphon to a white water outlet pipe.

Non insulated discharge pipes are potential sources of danger.

pressure drop 

for each bend (m)

45° 90° 

max. linear length 

concentric duct ø 60-100 (m)

26 MIX C.S.I.

3,40

30 MIX C.S.I.

3,40

30 MIX R.S.I.

3,40

35 MIX C.S.I.

2

35 MIX R.S.I.

2

1

1,5

pressure drop 

for each bend (m)

45° 90° 

length of ducts

vertical and horizontal (m)

26 MIX C.S.I.

7,93 - 7,61

30 MIX C.S.I.

7,93 - 7,61

30 MIX R.S.I.

7,93 - 7,61

35 MIX C.S.I.

4,58 - 4,26

35 MIX R.S.I.

4,58 - 4,26

1,35

2,2

Summary of Contents for C.A.I.

Page 1: ...IX C S I MIX R S I EN INSTALLER AND USER MANUAL ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO FR MANUEL D INSTALLATION ET D UTILISATION HU TELEP T I S FELHASZN L I K ZIK NYV RO MANUAL...

Page 2: ...lectromagn tica 2004 108 CE Directiva baja tensi n 2006 95 CE y por lo tanto es titular de la marca CE Portug es A caldeira EXCLUSIVE est conforme com os requisitos essenciais das seguintes Directivas...

Page 3: ...s modelos C A I MIX C S I y R A I MIX R S I ver dibujo Rogamos consulten el manual para encontrar las instrucciones relativas a su modelo de caldera Espa ol En algunas partes del manual se utilizan lo...

Page 4: ...ehajtani R S I A haszn lati meleg v zre vonatkoz adatok csak forr v z t rol csatlakozta t sa eset ben kell figyelembe venni a t rol k l n rendelhet tartoz k R A I R S I Paragrafele referitoare la func...

Page 5: ...all contractual and non contractual liability for injury to persons or animals or damage to property deriving from errors made during installation adjustment and servicing and from improper use This...

Page 6: ...g screw C fig 3c pull the cover towards you and remove A B fig 4a loosen the fixing screws D and remove the shell fig 3a lift up the panel and turn it forwards open the terminal board covers making th...

Page 7: ...mmon chimney suction and exhaustion in the same chimney C32 C32x Concentric roof exhaustion Outlets like C12 C42 C42x Exhaustion and suction in common separate chimneys but subject to similar wind con...

Page 8: ...e collector can only be applied to the fumes outlet within 0 85 m from the boiler connect the trap of the condensate collector to a waste water drain The fumes outlet duct must slope by 1 towards the...

Page 9: ...bar 28 30 37 28 30 37 28 30 37 28 30 37 28 30 37 Category MT I3B P I3B P I3B P I3B P I3B P LPG pressure G30 G31 mbar 30 30 30 30 30 Hydraulic connections CH input output 3 4 3 4 3 4 3 4 3 4 DHW input...

Page 10: ...O 120 33 285 52 367 10 Maximum pressure downstream DHW valve mbar 11 80 28 00 36 00 mm H2 O 120 33 285 52 367 10 Minimum pressure downstream CH valve mbar 2 10 5 00 6 70 mm H2 O 21 41 50 99 68 32 Mini...

Page 11: ...in burner 15 nozzles mm 1 35 0 76 0 76 CH maximum gas capacity Sm3 h 3 51 kg h 2 62 2 58 DHW maximum gas capacity Sm3 h 3 51 kg h 2 62 2 58 CH minimum gas capacity Sm3 h 1 04 kg h 0 77 0 76 DHW minimu...

Page 12: ...e reaches 1 to 1 5 bar The boiler produces heating and domestic hot water The control panel fig 13 contains the main boiler control and management functions Fig 13 Fig 14 Domestic hot water temperatur...

Page 13: ...about 4 seconds after the cycle ends The display will look like fig 16 If the test is unsuccessful the boiler will not work and a 0 will flash on the display In this case contact the Technical Assista...

Page 14: ...ture to a safe value 35 C The symbol lights up on the display circulator anti block one operating cycle is performed every 24 hours Switching off for long periods For prolonged absences press the butt...

Page 15: ...pressure fig 31 Fig 31 Fig 32 Fig 33 S A R A BOOSTER function If the winter comfort mode is selected the S A R A Booster fun ction is activated for the heating circuit and reaches the required ambient...

Page 16: ...tre 3 Viewing the and symbols fig 39 Contact the Technical Assistance Centre Note Fault in domestic hot water circuit sensor 60 the boiler works regularly but does not ensure the stability of the hot...

Page 17: ...ssist centre 1 GAS TYPE 1 Methane 1 2 2 LPG 3 Methane France 2 BOILER POWER 26 26kW 26 30 34 30 30kW 34 35kW 3 INSULATION LEVEL OF BUILDING min 5 20 5 10 DHW MODE 0 OFF 1 1 Instantaneous 2 Mini tank 3...

Page 18: ...ter tank Setting parameters selector cases A B and C using in calibration and programmation phase Function key ON the boiler is electrically powered and waiting for opera ting requests OFF the boiler...

Page 19: ...re is increased About 4 seconds after the selection has been made the modification is memorised and the display returns to the delivery temperature read by the sensor Fig 50 When powered the boiler pe...

Page 20: ...afety values the circulator and the burner work at minimum power to increase the water temperature to a safe value 35 C The symbol lights up on the display circulator anti block one operating cycle is...

Reviews: