C.A.I.: programmable parameters
N° DESCRIPTION
PARAMETERS
UNIT OF
MIN
MAX
DEFAULT
PARAMETERS
PAR.
MEASURE
(setted in factory)
(setted by techn. assist. centre)
1 GAS
TYPE
1
Methane
1-2
2
LPG
3 Methane France
3
INSULATION LEVEL OF BUILDING (+) (*)
min
5
20
5
10
DHW MODE
0 (OFF)
1
1
(Instantaneous)
2
(Mini-tank)
3 (External water-tank with thermostat)
4 (External water-tank with sensor)
11
DHW CIRCUIT MAXIMUM SET-POINT
° C
40
60
60
12
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
60
13
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
80
14
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
5
20
CH MODE
0 (OFF)
1
1
(ON)
2 (zone remote control panel)
21
HEATING CIRCUIT MAXIMUM SET-POINT
° C
40
80
80
22
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
40
28
MAX HEATING POWER REDUCTION TIMER
min
0
20
15
29
FORCED HEATING SHUT DOWN TIMER
min
0
20
3
30
HEATING TIMER RESET FUNCTION
-
0
1
0
40
DHW THERMOSTAT OPERATING MODE
0 (OFF)
1
1
(AUTO)
2
(ON)
41
DHW PREHEATING FUNCTION
0 (OFF)
1
1
(AUTO)
2
(ON)
42
S.A.R.A. FUNCTION
0 (OFF)
1
1
(AUTO)
43
S.A.R.A. BOOSTER FUNCTION
0 (OFF)
1
1
(AUTO)
44
THERMOREGULATION FUNCTION
0 (OFF)
1
1
(AUTO)
45
INCLINATION THERMOREGULATION CURVE (OTC) (*)
-
2,5
40
20
48
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
0
50
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
61
DHW ANTIFREEZE FUNCTION TEMPERATURE (ON)
°C
0
10
4
62
HEATING ANTIFREEZE FUNC. DELIVERY TEMP. (ON)
°C
0
10
6
85
SEMI-AUTOMATIC FILLING
0 (disabled)/1 (enabled)
1
86
AUTOMATIC FILLING PRESSURE (ON)
bar
0.4
0.8
0.6
MIX C.S.I.: programmable parameters
N° DESCRIPTION
PARAMETERS
UNIT OF
MIN
MAX
DEFAULT
PARAMETERS
PAR.
MEASURE
(setted in factory)
(setted by techn. assist. centre)
1 GAS
TYPE
1
Methane
1-2
2
LPG
3 Methane France
2
BOILER POWER
26 (26kW)
26-30-34
30
(30kW)
34
(35kW)
3
INSULATION LEVEL OF BUILDING (+) (*)
min
5
20
5
10
DHW MODE
0 (OFF)
1
1
(Instantaneous)
2
(Mini-tank)
3 (External water-tank with thermostat)
4 (External water-tank with sensor)
11
DHW CIRCUIT MAXIMUM SET-POINT
° C
40
60
60
12
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
60
13
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
80
14
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
5
20
CH MODE
0 (OFF)
1
1
(ON)
2 (zone remote control panel)
21
HEATING CIRCUIT MAXIMUM SET-POINT
° C
40
80
80
22
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
40
28
MAX HEATING POWER REDUCTION TIMER
min
0
20
15
29
FORCED HEATING SHUT DOWN TIMER
min
0
20
3
30
HEATING TIMER RESET FUNCTION
-
0
1
0
40
DHW THERMOSTAT OPERATING MODE
0 (OFF)
1
1
(AUTO)
2
(ON)
41
DHW PREHEATING FUNCTION
0 (OFF)
1
1
(AUTO)
2
(ON)
42
S.A.R.A. FUNCTION
0 (OFF)
1
1
(AUTO)
43
S.A.R.A. BOOSTER FUNCTION
0 (OFF)
1
1
(AUTO)
44
THERMOREGULATION FUNCTION
0 (OFF)
1
1
(AUTO)
45
INCLINATION THERMOREGULATION CURVE (OTC) (*)
-
2,5
40
20
48
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
0
50
THIS PARAMETER IS NOT USED ON THIS MODEL. DO NOT MODIFY
1
61
DHW ANTIFREEZE FUNCTION TEMPERATURE (ON)
°C
0
10
4
62
HEATING ANTIFREEZE FUNC. DELIVERY TEMP. (ON)
°C
0
10
6
85
SEMI-AUTOMATIC FILLING
0 (disabled)/1 (enabled)
1
86
AUTOMATIC FILLING PRESSURE (ON)
bar
0.4
0.8
0.6
(*) parameters shown only with external sensor connected and parameter 44 in 1 (AUTO).
(+) for well-insulated buildings select values close to 20, for badly insulated buildings choose values close to 5.
T m. =
maximum rated temperature of heating water
T e. =
minimum rated external temperature
OTC =
10 x
Tm. - 20
20 - Te.
Parameter 45 “Inclination of thermoregulation curve (OTC)”
The curve must be chosen according to the geographical area and the type of
installation.