8
Bentone
2.2.2 Capacity range
Capacity kW
Gas quantity
at min. power
Nm
3
/h
1
)
Gas quantity
at max. power
Nm
3
/h
1
)
Max. connection
pressure mbar
Min connection
pressure mbar
see data plate
Lower heat value Hu at normal state 15°C and 1013.25 mbar EN676
Grade of gas
Natural gas
Natural gas
Butane
Propane
Biogas
Gas quantity and capacity vary according to grade of gas and connection
pressure.
BG450
G20 120-550
12,6
57,9
360
G25 120-550
14,6
67,1
360
G30 120-550
3,7
16,9
360
G31 120-550
4,9
22,4
360
kWh/Nm
3
MJ/Nm
3
kcal/Nm
3
G20
9.5
34.02
8126
G25
8.2
29.25
6986
G30
32.5
116.09
27728
G31
24.6
88.00
21019
6,0
21,60
5159
2.2.3 Appliance categories
Only dry gas is permitted for use
Max operating current, see data plate.
Gerätekategorien
Appliance categories
Versorgungsdrücke
Supply pressures
Bestimmungsländer
Countries of destination
II
2R/3R
20-360mBar
AT, BE, BG, CZ, CY, HR,
DK, FI, FR, DE, GB, HU, IS,
IE, IT, LV, LT, LU, MT, NL,
NO, PL, PT, MK, RO, RS,
SK, SS, ES, SE, CH, TR, GB,
EE
II
2H38/P
20-360mBar
AT, CH, CY, DK, FI, LT, RO,
SE, SK
II
2H3P
20-360mBar
GB, IE
II
2L38/P
20-360mBar
NL, RO
II
2E38/P
20-360mBar
PL
II
2E(R)B
20-360mBar
BE
I
3P
20-360mBar
BE
/2
172 525 23
2020-10-29
Summary of Contents for BG 450
Page 18: ...18 Bentone 4 10 Gas nozzle 45 Natural gas Propan Biogas UV detector...
Page 36: ...36 Bentone 172 615 77 2020 10 21 2 10 2 Wiring diagram BG450 2 BP S4...
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...