32
Bentone
172 615 88-2 2022-09-08
Components
Service life – Recommended
replacement
Service life – Recommended
replacement Operating cycles
Control system
10 years
250,000 starts
Valve control system
10 years
250,000 starts
Pressure switch
10 years
250,000 starts
Ignition system with fl ame guard
10 years
250,000 starts
UV fl ame sensor
10,000 h
N/A
Gas pressure controls
15 years
N/A
Gas valve without leak testing
10 years
250,000 starts
Gas valve with leak testing
Replacement upon fault detection
N/A
Gas pressure switch
10 years
250,000 starts
Safety blow-off system
10 years
N/A
Damper motor
N/A
500,000 starts
Contactor
10 years
500,000 starts
Burner
1 year
3,000 h
Inspection of electrical installation
1 year
3,000 h
Leak check
1 year
3,000 h
Filter
1 year, replacement at Δp>10 mbar
3,000 h, replacement at Δp>10 mbar
Electrodes
Replacement/cleaning 1 year
Replacement/ceaning 3,000 h
Brake plate
Replacement/cleaning 1 year
Replacement/ceaning 3,000 h
Motor
1 year
3,000 h
Fan wheel
1 Year
Replace if need for cleaning/imbalance
3,000 h
Replace if need for cleaning/imbalance
The burner and its components must be recycled according to applicable regulations.
11. Service
Service and maintenance work may only be performed by qualifi ed
personnel. Perform operational check of all safety systems and components
at each service. Only Enertech original parts should be used when replacing
components.
!
Use caution when operating the burner, surfaces may be hot.
11.1 Burner Service Schedule, Gas
Servicing must be carried out once a year or after 3,000 hours of operation.
11.2 Component replacement intervals