33
Bentone
172 615 01-2
!
When servicing/replacing components that affect combustion,
flue gas analysis and soot test shall be carried out on the
installation.
11.3 Combustion device
1.
Disconnect the main power and shut off the fuel supply.
2.
Loosen screws (A) and swing the burner out.
3.
Disconnect the ignition and ionisation cables.
4.
Check the position of the combustion device. Loosen screw (B) to
remove the adjustment device.
5.
Loosen screw (C) and remove the combustion device.
6.
Check and clean the brake plate and gas inlet, replacing components
if necessary.
7.
Check the ignition and ionisation electrodes, replace if necessary (see
chapter Gas nozzle).
8.
Refit the combustion device in reverse order.
9.
Press the burner together and lock with screws (A).
10. Turn on the main power and open the fuel supply.
11. Start burner and check/adjust combustion.
!
Before obtaining access to electrical and fuel line components
all supply circuits must be disconnected.
!
Check for leaks in the gas line.