ELECTRIC EQUIPMENT

Oil burner control: LMO24.255

List of components

A1  Oil burner control

B1 Photoresistor

F1 Fuse

H1  Lamp, low capacity

H3  Lamp, lock-out signal 230 V

K1  Thermal overload protection

M1  Burner motor

P1  Time meter, low capacity    

 (optional)

P2  Time meter, high capacity    

 (optional)

S1  Operating switch

S2  Operating switch, high/low   

 capacity

S3  Control thermostat

S4  Temperature limiter

S5  Micro switch for hinged door

S6  Control thermostat, high/low

 capacity

S7  Main switch

T1  Ignition transformer

X1  Connection terminal board

X2  Earth terminal

X3  Plug-in contact "Euro", burner

X4  Plug-in contact "Euro", boiler

X5  Plug-in contact "Euro", 

 

high/low burner

X6  Plug-in contact "Euro", 

 

high/low boiler

Y1  Solenoid valve 1

Y2  Solenoid valve 2

Y2H Solenoid valve, Hydraulic piston

 

(Only 2-stage burners with

 

1 nozzle.)

If S6 is missing connection between T6 and T8.

Mains connection and fuse in accordance with local regulations.

Function

1. Switch on operating switch and twin thermostat

 

The burner motor starts, an ignition spark is formed, the prepurge goes

 

on till the prepurge period expires and the solenoid valve 1 opens (2).

2. Solenoid valve 1 opens

 

Oil mist is formed and ignited. The photocell indicates a fl ame.

3. The safety time expires

a.  If no fl ame is established before this time limit the control cuts out.

b.  If for some reasons the fl ame disappears after this time limit, the burner

 

will make an attempt to re-start.

4. Full load thermostat ON

 

The burner is in operating position and can now change between high

 

and low capacity.

4-5. Operating position

 

If the burner operation is interrupted by means of the main switch or the

 

thermostat, a new start takes place when the conditions in accordance

 

with point 1 are fulfi lled.

The oil burner control cuts out

 

A red lamp in the control is lit. Press the reset button and the burner

 re-starts.

Technical data

Pre-ignition time:   

25 s

Pre-purge time: 

 

26 s

Post-ignition time:   

5 s

Safety lock-out time: 

< 5 s

Reset time after lockout: 

 

< 1 s

Reaction time on fl ame failure: 

 

< 1 s

Ambient temperature: 

from - 20 to +60°C

Min. current with fl ame established: 

45µ A

Max. photo current at start: 

 

5,5µ A

Enclosure: 

 

IP 40

Control of photo current

Current through photo unit is measured with a d.c. ammeter (a moving coil 

instrument connected in series with the photo unit).

171 435 26  09-01

2(3)

Summary of Contents for B30A2.2H

Page 1: ...Providing sustainable energy solutions worldwide 178 066 52 1 2016 04 18 Installation and maintenance instruction B30A2 2H B30A2 2HL...

Page 2: ......

Page 3: ...Cover inspection glass 10 Switch I II 11 Switch I 0 12 Fan wheel 13 Motor 14 Nozzle assembly adjustment 15 Blast tube 16 Photo cell 17 Adjustment device 18 Indication air damper 19 Connecting pipe St...

Page 4: ...range and nozzles recommended The net calori c value of 11 86 kWh kg for light oil has been used 188 415 B 372 108 108 220 303 281 160 190 108 35 Recommended nozzle Because of different boiler types e...

Page 5: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Page 6: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Page 7: ...ge Set the operating switch S2 on low capacity I Loosen the screw A and turn the damper to the position wan ted Tighten the screw A again Second stage Set the operating switch S2 on high capacity II S...

Page 8: ...at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A and nut B Service of burner head 171 305 47 09 01 1 Loosen or swing out the burne...

Page 9: ...l burner control LMO24 255 Wiring diagram ELECTRIC EQUIPMENT 1 3 1N 50 60 Hz 230 V If the boiler is not equipped with wired contacts connect the enclosed contacts to terminals X4 and X6 in accordance...

Page 10: ...on till the prepurge period expires and the solenoid valve 1 opens 2 2 Solenoid valve 1 opens Oil mist is formed and ignited The photocell indicates a ame 3 The safety time expires a If no ame is est...

Page 11: ...the problem by pressing and holding the reset button for 3 seconds The number of ashes below is repeated with a pause in between 2 ashes No ame signal when safety time expires 4 ashes False light dur...

Page 12: ...length in metres at a nozzle capacity of 9 5 Gph Max permissible pres sure at the suction and pressure side is 2 0 bar Components 1 Nozzle outlet G 1 8 Stage 2 2 Pressure gauge port G 1 8 3 Nozzle out...

Page 13: ...it is assured by a bleed at on the piston In one pipe operation a high pressure connection must be loosened until the air is evacuated from the system Cut Off The solenoid valves of the A2L pump are o...

Page 14: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Page 15: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Page 16: ...of magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photoce...

Page 17: ...sont conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suiv...

Page 18: ...he burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Page 19: ......

Page 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Reviews: