background image

FAULT LOCATION

Burner fails to start

Delayed ignition, burners starts violently

Burner fails to start after normal operation

Situation

Motor runs

Burner pre-purges

Flame occurs

Burner locks out

Motor runs

Burner pre-purges

No fl ame occurs

Burner locks out

Possible causes

Flame instability

Incorrect head settings

Low oil pressure

Excess air

Photocell not seeing light

Photocell failed

Control faulty

False light

No spark

No oil

Remedies

Check nozzle to burner head dimension 

and electrode position

Check oil pressure

Adjust air damper

Check that photocell is clean and 

unobstructed

Confi rm with new photocell

Confi rm with new control. (NB. it is 

advisable to change the photocell if also 

changing control)

Check that photocell is not seeing 

ambient light

Check that H.T. leads are sound and are 

not arcing other than at electrode gap

Check oil supply to burner - check that 

pump is not airlocked

Check operation of magnetic valve

Burner fails to start

Lamp not lit

Motor runs

 

Burner runs to lockout

Fuse has blown

Appliance thermostat has not reset

Appliance overheat device has operated

Control relay or photocell defective

No oil being delivered

Excessive fl ue draught is preventing 

 

fl ame establishment

No spark

Check or replace fuse if necessary. 

Check reason for failure

Adjust thermostat

Reset overheat device. Find reason for 

its operation and rectify

Check by replacement

Check that tank, oil lines, fi re valve, pump 

and nozzle are all in good order

Rectify condition

Check ignition transformer. Check 

electrode gap and porcelain

Burner pulsates on start-up 

only with hot fl ue

Burner pulsates on start-up

Burner starts violently

Excessive draught

Nozzle partly blocked

Oil pressure too low

Flue blocked or damaged

Fan slipping on shaft

Pump coupling loose or worn

Delayed ignition

Adjust the burner

Replace nozzle

Check and adjust
Check and rectify

Check and retighten

Check and replace

Check the electrode adjustment, see 

diagram

Check electrodes for damage

Check H.T. leads for damage and 

disconnection

171 915 01  08-01

Försäkran om överensstämmelse
Declaration of conformity
Konformitätserklärung
Déclaration de conformité

Brännare, Burner, Ölbrenner, Brûleur 
Certifi kat TÜV Süddeutschland
Certifi kat nr. 

Typ, Type:

08128915006 

BF 1

0111110535004 

B 1

0207110535005 

B 2

02119815001 

 ST 97, ST 108, ST 120, 
ST 133, ST 146

02119815002 

B 9, B 10, B 11

Certifi kat nr. 

Typ, Type:

02119815003 

B 20, B 30, B 40, B 45

02119815004 

B 50, B 60, B 70, B 80

040588622001 

B 55

040588622002 

B 65

13129815007 

B 45 MF, B 45-2 MF

Enertech AB försäkrar under eget ansvar att ovannämnda produkter är i överensstämmelse med  följande standarder eller andra 
regelgivande dokument och uppfyller tillämpliga delar i EU direktiv.

Enertech AB declares under sole responsibility that the above mentioned product is in conformity with the following standards or other 
normative documents and follows the provisions of applicable parts in the following EU Directives.

Enertech AB erklärt in eigener Verantwortung, dass obenstehende Produkte mit folgenden Normen oder anderen normativen 
Dokumenten und anwendbare Teile in EU-Direktiven in Übereinstimmung stehen

Enertech AB déclare sous sa seule responsabilité que les produits désignés ci-dessus sont conformes aux normes et aux documents 
normatifs suivants et satisfont aux critères applicables des directives CE suivantes:

Dokument: 

EN 267

  EN 

60335

EU direktiv. EU Directives, EU-Direktiven, CE suivantes:

2004/108/EC 

 Elektromagnetisk kompatibilitet, Electromagnetic compatibility EC-Richtlinie, Compatibilité électromagnétique

2006/95/EC 

 Lågspänningsdirektivet, Low-voltage directive, Niederspannungs-Richtlinie, Directive sur les basses tensions

2006/42/EC 

 Maskindirektivet, Machinery directive, Maschinen-Richtlinie, Directive sur les machines

92/42/EEC 

 Verkningsgradsdirektivet, Effi ciency directive, Wirkungsgrad-Richtlinie, Directive sur les exigences de rendement

Genom att brännaren uppfyller ovannämnda standarder och direktiv erhåller brännaren CE - märkningen.

In that the burner conforms to the above mentioned standards it is awarded the CE mark.

Indem der Brenner die obengenannten Normen und Richtlinien erfüllt, erhält der Brenner die CE-Kennzeichnung.

Du fait de leur conformité aux directives mentionnées ci-dessus, les brûleurs Bentone bénéfi cient du marquage CE.

Enertech AB, Bentone Division/ 
är kvalitetscertifi erat enligt/ 
is quality certifi ed according to/ 
ist nach dem Qualitätsmanagement / 
est certifi ée à la norme de qualité 
SS-EN ISO 9001:2008

Ljungby, Sweden, 150227 (27/02/15)

ENERTECH AB Bentone Division

Box 309
SE-341 26 Ljungby Sweden

Håkan Lennartsson

171 901 06  15-01

Summary of Contents for B30A2.2H

Page 1: ...Providing sustainable energy solutions worldwide 178 066 52 1 2016 04 18 Installation and maintenance instruction B30A2 2H B30A2 2HL...

Page 2: ......

Page 3: ...Cover inspection glass 10 Switch I II 11 Switch I 0 12 Fan wheel 13 Motor 14 Nozzle assembly adjustment 15 Blast tube 16 Photo cell 17 Adjustment device 18 Indication air damper 19 Connecting pipe St...

Page 4: ...range and nozzles recommended The net calori c value of 11 86 kWh kg for light oil has been used 188 415 B 372 108 108 220 303 281 160 190 108 35 Recommended nozzle Because of different boiler types e...

Page 5: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Page 6: ...e an optimum adjust ment is obtained If larger nozzles are used the preadjustment of both the air volume and the nozzle assembly must be increased A whistling sound may be heard which can be eliminate...

Page 7: ...ge Set the operating switch S2 on low capacity I Loosen the screw A and turn the damper to the position wan ted Tighten the screw A again Second stage Set the operating switch S2 on high capacity II S...

Page 8: ...at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipes by loosening screw A and nut B Service of burner head 171 305 47 09 01 1 Loosen or swing out the burne...

Page 9: ...l burner control LMO24 255 Wiring diagram ELECTRIC EQUIPMENT 1 3 1N 50 60 Hz 230 V If the boiler is not equipped with wired contacts connect the enclosed contacts to terminals X4 and X6 in accordance...

Page 10: ...on till the prepurge period expires and the solenoid valve 1 opens 2 2 Solenoid valve 1 opens Oil mist is formed and ignited The photocell indicates a ame 3 The safety time expires a If no ame is est...

Page 11: ...the problem by pressing and holding the reset button for 3 seconds The number of ashes below is repeated with a pause in between 2 ashes No ame signal when safety time expires 4 ashes False light dur...

Page 12: ...length in metres at a nozzle capacity of 9 5 Gph Max permissible pres sure at the suction and pressure side is 2 0 bar Components 1 Nozzle outlet G 1 8 Stage 2 2 Pressure gauge port G 1 8 3 Nozzle out...

Page 13: ...it is assured by a bleed at on the piston In one pipe operation a high pressure connection must be loosened until the air is evacuated from the system Cut Off The solenoid valves of the A2L pump are o...

Page 14: ...93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14...

Page 15: ...1 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 9...

Page 16: ...of magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photoce...

Page 17: ...sont conformes aux normes et aux documents normatifs suivants et satisfont aux crit res applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suiv...

Page 18: ...he burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...

Page 19: ......

Page 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Reviews: