POSITIONING OF IGNITION ELECTRODE AND IONISATION PROBE
It is important that the spark electrode and the ionisation probe are correctly positioned over the burner bars to ensure
good ignition and flame detection. The probe and electrode should 3- 4 mm from the burner bar.
CLEANING THE HEAT EXCHANGER
The heat exchanger should only be cleaned by suitably qualified personnel It is recommended that the heat
exchanger by cleaned once a year prior to the start of the heating season The following procedure should be
carried out:
3-4-5-6-7
Remove
burner
(1)
from its housing after first having disconnected the gas solenoid valve;
Remove top panel
(2)
;
Remove inspection door
(3)
;
Remove flue manifold
(4)
;
Brush clean the heat exchanger elements
(5)
;
With a vacuum remove any soot deposits from the elements
(5)
;
Clean all heat exchanger external surfaces;
Re assemble in reverse order ensuring that there is a good seal replacing any seals and gaskets as necessary.