INITIAL START UP SINGLE STAGE
29
VENTILATION
Switch on mains supply to the equipment
Set On/ Standby switch to ON
Set the remote control panel switch to VENT check that
fans rotation is correct
HEAT
Set the remote control panel to HEAT
Set the room thermostat to the desired temperature
The flue venter will start, activating the differential
pressure switch
After a short period ignition takes place after one minute
the air flow fan will start
When desired room temperature is reached the burner
will stop the fan will overrun for approximately 3-4
minutes.
IGNITION
Connect the manometer on the pressure test point
on the gas manifold
Set mains isolator to On
Open gas isolator cock
Set the on/standby switch to ‘On’
Set heat/vent switch to Heat
Set the room thermostat to the desired temperature
Reset any lockout in the system as indicated by the
red or yellow lights
The flue venter will start up activating the differential
pressure switch.
The heater will pre purge the combustion chamber the
electronic control box will supply the ignition electrode
and the gas valve simultaneously.
If the gas line has not been correctly purged ignition
may not take place at the first attempt resulting in
lockout of the burner.
Reset button and repeat.
Before each attempt at ignition it is
necessary to wait at least 10 seconds
When the burner has ignited check the manometer and,
adjust gas pressure setting to pressure indicated on data
plate, adjust by turning the solenoid valve screw on gas
valve.
Check the gas consumption reading corresponds
with that indicated in the TECHNICAL DATA section
Set on/standby switch to ‘standby’. When heater is
sufficiently cool Isolate electrical supply Isolate gas
supply
Remove the manometer and ensure the screw at the
test point is tightened to avoid any gas leaks
Open the gas isolating cock Switch on electrical
supply
Set the room thermostat to the desire temperature.
The heater is now ready for operation.
WARNING!
The heater must only be operated with the
burner compartment door(s) closed.
STOPPING
To stop the heater using only the room thermostat. Set it
to the minimum temperature. Fan will stop after about 3-
4 minutes. If required, switch off the mains current at the
isolator.
WARNING
If Heater is to be switched off for a Long Period set
ON/STANDBY switch to STANDBY.
Isolate at mains electrical supply
Isolate the gas supply.