P
ropane (G31 I
3P
) Cabinet Heater
The minimum allowable pre-purge time requires calculating [BS EN1020:1998 clause 6.38].
To do this only the Carbon Dioxide CO
2
figure needs to be measured.
E.G. on a model 125 the calculated minimum time is = 490.7 / ((300 / CO2) + 2.01)
If the measured CO
2
is 11.2%
Then 300 / 11.2 = 26.79
26.79 + 2.01 = 28.8
Therefore minimum pre-purge time is = 490.7/28.8 =
17.0 seconds
The calculation to be conducted is given below for all models:
Model 100
Minimum pre-purge time = 611.2 / ((300 / CO2) + 2.01)
Model 125
Minimum pre-purge time = 490.7 / ((300 / CO2) + 2.01)
Model 150
Minimum pre-purge time = 399.9 / ((300 / CO2) + 2.01)
Model 200
Minimum pre-purge time = 785.2 / ((300 / CO2) + 2.01)
Model 250
Minimum pre-purge time = 621.5 / ((300 / CO2) + 2.01)
Model 300
Minimum pre-purge time = 515.4 / ((300 / CO2) + 2.01)
Model 400
Minimum pre-purge time = 539.0 / ((300 / CO2) + 2.01)
Model 500
Minimum pre-purge time = 477.3 / ((300 / CO2) + 2.01)
Model 600
Minimum pre-purge time = 458.2 / ((300 / CO2) + 2.01)
Model 700
Minimum pre-purge time = 383.9 / ((300 / CO2) + 2.01)
Model 800
Minimum pre-purge time = 585.9 / ((300 / CO2) + 2.01)
Model 1000
Minimum pre-purge time = 484.0 / ((300 / CO2) + 2.01)
Model 1200
Minimum pre-purge time = 735.4 / ((300 / CO2) + 2.01)
Model 1300
Minimum pre-purge time = 667.5 / ((300 / CO2) + 2.01)
The pre-purge time must then be measured. If the measured pre-purge time is lower
than the calculated time STOP and contact Benson Heating.
Summary of Contents for G20 I2H
Page 8: ......
Page 24: ...Motorised Fan Assembly 100 300 Fan and Motor Assembly 400 700 Fan and Motor Assembly 800 1300...
Page 31: ...Wiring Diagram 20 45 421 400 500 ON OFF Riello Gas or Oil Fired Burner SC FM 230 50 1ph 6A MCB...
Page 33: ...Wiring Diagram 20 45 420 100 300 ON OFF Riello Gas or Oil Fired Burner Remote SC SZ 230 50 1ph...
Page 34: ...Wiring Diagram 20 45 422 400 500 ON OFF Riello Gas or Oil Fired Burner Remote SC SZ 230 50 1ph...
Page 43: ......
Page 58: ......
Page 59: ......