The minimum allowable pre-purge time requires calculating [BS EN1020:1998 clause 6.38].
To do this only Carbon Dioxide CO
2
figure needs to be measured.
E.G. on a model 300 the calculated minimum time is = 203.6 / ((100 / CO2) + 1)
If the measured CO
2
is 9.7%
Then 100 / 9.7 = 10.3
10.3 + 1 = 11.3
Therefore minimum pre-purge time is = 203.6 / 11.3 =
18.0 seconds
The calculation to be conducted is given below for all models:
Model 100
Minimum pre-purge time = 241.4 / ((100 / CO2) + 1)
Model 125
Minimum pre-purge time = 193.8 / ((100 / CO2) + 1)
Model 150
Minimum pre-purge time = 157.9 / ((100 / CO2) + 1)
Model 200
Minimum pre-purge time = 310.1 / ((100 / CO2) + 1)
Model 250
Minimum pre-purge time = 245.5 / ((100 / CO2) + 1)
Model 300
Minimum pre-purge time = 203.6 / ((100 / CO2) + 1)
Model 400
Minimum pre-purge time = 212.9 / ((100 / CO2) + 1)
Model 500
Minimum pre-purge time = 188.5 / ((100 / CO2) + 1)
Model 600
Minimum pre-purge time = 181.0 / ((100 / CO2) + 1)
Model 700
Minimum pre-purge time = 151.6 / ((100 / CO2) + 1)
Model 800
Minimum pre-purge time = 231.4 / ((100 / CO2) + 1)
Model 1000
Minimum pre-purge time = 191.2 / ((100 / CO2) + 1)
Model 1200
Minimum pre-purge time = 293.2 / ((100 / CO2) + 1)
Model 1300
Minimum pre-purge time = 263.7 / ((100 / CO2) + 1)
The pre-purge time must then be measured. If the measured pre-purge time
is lower than the calculated time STOP and contact Benson Heating
.
Summary of Contents for G20 I2H
Page 8: ......
Page 24: ...Motorised Fan Assembly 100 300 Fan and Motor Assembly 400 700 Fan and Motor Assembly 800 1300...
Page 31: ...Wiring Diagram 20 45 421 400 500 ON OFF Riello Gas or Oil Fired Burner SC FM 230 50 1ph 6A MCB...
Page 33: ...Wiring Diagram 20 45 420 100 300 ON OFF Riello Gas or Oil Fired Burner Remote SC SZ 230 50 1ph...
Page 34: ...Wiring Diagram 20 45 422 400 500 ON OFF Riello Gas or Oil Fired Burner Remote SC SZ 230 50 1ph...
Page 43: ......
Page 58: ......
Page 59: ......