TEBEVERT III INVERTER SYSTEM (120 VDC)
07.11.2011
36
028-0009-006
4.3.6
AC CABLE REQUIREMENTS FOR 25kVA,
220VAC AC INPUT SYSTEM
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
220VAC /150A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2:L1/L2/PE
5 inverters
Compression Type
2 AWG - 4/0
150A
4.3.7
AC CABLE REQUIREMENTS FOR 25kVA,
240VAC AC INPUT SYSTEM
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
120/240VAC /150A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2:L1/L2/PE
5 inverters
Compression Type
2 AWG - 4/0
150A
4.3.8
AC CABLE REQUIREMENTS FOR 25kVA,
480VAC AC INPUT SYSTEM
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
480VAC /70A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2:L1/L2/PE
5 inverters
Compression Type
2 AWG - 4/0
70A