TEBEVERT III INVERTER SYSTEM (120 VDC)
07.11.2011
33
028-0009-006
Warning!
For the proper protection of the load circuits careful
attention must be paid to the selection of upstream the
mains protection.
The voltage-free fault messaging contact are rated for a
maximum of 230VAC/1A or 270VDC/0.2A (50W max).
If a future inverter expansion is planned, the cable cross-
sections and the fuse protection must be used for the
maximum values of load power requirements.
Warning!
If an external battery is connected to the DC inputs of the
inverter, then the instructions concerning the installation
and maintenance given by the manufacturer of the battery
must be observed.
The supply circuits must be equipped with a disconnecting
device. It must be mounted close to the cabinet and easily
accessible.
The system has high leakage current. Earth connection is
essential before connecting supply