TEBEVERT III INVERTER SYSTEM (120 VDC)
07.11.2011
35
028-0009-006
4.3.3
AC CABLE REQUIREMENTS FOR 25kVA,
120VAC AC INPUT RATINGS
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
120VAC/250A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2: L1/N/PE
5 inverters
Compression Type
2 AWG - 4/0
250A
4.3.4
AC CABLE REQUIREMENTS FOR 25kVA,
120/240VAC AC INPUT SYSTEM
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
120/240VAC/150A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2: L1/L2/PE
5 inverters
Compression Type
2 AWG - 4/0
150A
4.3.5
AC CABLE REQUIREMENTS FOR 25kVA,
208VAC AC INPUT SYSTEM
Supply conductor
Maximum system
capacity
Suggested rating of
disconnect device
Mains
5 inverters
120/208VAC/150A
Terminal
designation
Connection
type
Terminal/connection
capacity
Suggested
protection
X2:L1/L2/PE
5 inverters
Compression Type
2 AWG - 4/0
150A