7

(27)

CHIUDE= CLOSE button input (n.o. contact).

(28,29) ANT.= Input of radio board antenna

(30,31) RX 2CH.= Radio board 2nd channel contact (n.o. contact).

J2

SENS_H= Input for optional anti-crash card ”DA.AS”

If this control unit is not used, the central pins 2, 3 should be short-circuited.

Dip-switch functions
N.B.:

Every change of functions have to be done without electricity.

DSW1=

This selects the type of functioning of the P.P. button and Remote control.
Off= ”OPEN” - ”STOP” - ”CLOSE” functioning
On= ”OPEN” - ”CLOSE” - ”OPEN” functioning.

DSW2=

This enables or disables the automatic re-closing.
Off= Automatic re-closing enabled
On= Automatic re-closing disabled

DSW3=

This enables or disables the apartment building function (after the first opening command, the
P.P. button and the Remote control are deactivated).
Off= Apartment building function disabled.
On= Apartment building function enabled.

DSW4=

This enables or disables the pre-blinking function
Off= Pre-blinking disabled.
On= Pre-blinking enabled.

DSW5=

This selects the type of intervention of the ”FTC” input on opening
Off= No intervention
On= Temporary  stop

DSW6=

Select the type of stop controlled by the ”P.P.” push-button.
Off= The stopping in the opening phase allows the automatic closure (if enabled).
On= The stopping in the opening phase inhibits the automatic closure.

DSW7=

It enables or disables the rounds sensor triggering in the opening phase.
Off= Round sensor triggering enabled.
On= Rounds sensor triggering disabled.

DSW8=

Enables/Disables the reversion of movement controlled by the “ASC” input, after the activation
of the closing limit switch. This function permits to connect a sensitive rubber edge on the
edge of the gate closing leaf avoiding that the sensitive device causes the movement reversion
when the door must be completely closed. The closing limit switch should be positioned so
that it is triggered when a few centimetres are missing to the complete closure of the gate.
Off= Enabled: the “ASC” input always controls the movement reversion for some centimetres.
On = Disabled: After the activation of the closure limit switch, the “ASC” input stops the motor.

DSW9=

Spare.

DSW10= Spare.

Trimmer functions
TCA=

This allows the automatic re-closing time to be adjusted when this is enabled by positioning the
DSW2 Dip-switch on OFF.
Adjustment can be from a minimum of 10 to a maximum of 200 seconds.
The minimum time is obtained by rotating the trimmer completely anticlockwise.

TL=

This allows the working time of the automation to be adjusted. If the limit switches fail, the soft-
ware protection will intervene after this time has elapsed.
(Add about 4 sec. to the actual stroke time of the automation).
Adjustment can be from a minimum of 10 to a maximum of 200 seconds.
The minimum time is obtained by rotating the trimmer completely anticlockwise.

Summary of Contents for DA.C15

Page 1: ...ONTR LEUR CENTRALITA A MICROPROCESADOR AUTOMATISMI PER CANCELLI L8542603 Rev 04 00 01 Libro istruzioni Operating instructions Betriebsanleitung Livret d instructions Libro de instrucciones UNIONE NAZI...

Page 2: ...standards in particular Angewendete harmonisierte Normen insbesondere Normes harmonis e utilis es notamment Normas armonizadas utilzadas particularmente EN 55022 EN 61000 3 2 EN 61000 3 3 EN 50082 1 N...

Page 3: ...D4 D21 D24 D23 D26 D25 D28 R44 R45 R46 R17 R51 R50 R49 R48 R47 C20 C21 C22 C25 1 C2 D2 D29 D2 P1 C17 C1 VDR2 D5 C5 U4 U3 C18 J1 J3 C5 C7 J2 C19 C8 Q1 U1 D6 C3 PGM POWER RTX TCA TL C4 2 3 4 5 6 7 8 9 1...

Page 4: ...50Hz rispettare fase neutro 1 Neutro o L1 2 Fase o L2 3 L3 4 5 6 SELEZIONE TENSIONE DI ALIMENTAZIONE Collegare i morsetti 4 e 5 se la centrale alimentata a 230Vac Collegare i morsetti 6 e 5 se la cen...

Page 5: ...ra automatica DSW7 Abilita o disabilita l intervento del sensore di giri durante la fase di apertura Off Intervento sensore di giri abilitato On Intervento sensore di giri disabilitato DSW8 Abilita di...

Page 6: ...se or L2 3 L3 4 5 6 SELEZIONE TENSIONE DI ALIMENTAZIONE Connect terminals 4 and 5 if the control unit is powered at 230VAC Connect terminals 6 and 5 if the control unit is powered at 380VAC 7 8 9 APRE...

Page 7: ...e DSW7 It enables or disables the rounds sensor triggering in the opening phase Off Round sensor triggering enabled On Rounds sensor triggering disabled DSW8 Enables Disables the reversion of movement...

Page 8: ...30 380VAC Zufuhr Steuerung 230 380VAC 50Hz Phase Neutral beachten 1 Neutral oder L1 2 Phase oder L2 3 L3 4 5 6 SELEZIONE TENSIONE DI ALIMENTAZIONE Die Klemmen 4 und 5 verbinden wenn die Zentrale mit 2...

Page 9: ...as Anhalten beim ffnen schlie t den automatischen Schlie vorgang aus DSW7 Der Umdrehungsgeber wird hiermit beim ffnen freigegeben oder ausgeschaltet Off Umdrehungsgeber freigegeben On Umdrehungsgeber...

Page 10: ...nction Entr es Sorties 1 2 3 INPUT 230 380VAC Alimentation centrale 230 380Vc a 50Hz respecter phase neutre 1 Neutre ou L1 2 Phase ou L2 3 L3 4 5 6 SELEZIONE TENSIONE DI ALIMENTAZIONE Brancher les bor...

Page 11: ...fermeture automatique DSW7 Valide ou invalide l intervention du capteur de tours durant l ouverture Off Intervention du capteur de tours valid e On Intervention du capteur de tours invalid e DSW8 Vali...

Page 12: ...50Hz respetar fase neutro 1 Neutro o L1 2 Fase o L2 3 L3 4 5 6 SELEZIONE TENSIONE DI ALIMENTAZIONE Conectar los bornes 4 y 5 si la central est alimentada con 230VCA Conectar los bornes 6 y 5 si la cen...

Page 13: ...nte la fase de apertura OFF Intervenci n habilitada del sensor de vueltas ON Intervenci n inhabilitada del sensor de vueltas DSW8 Habilita inhabilita la inversi n mandada por la entrada ASC tras la ac...

Page 14: ...14...

Page 15: ...15...

Page 16: ...AUTOMATISMI PER CANCELLI AUTOMATISMI BENINC Srl Via Capitello 45 36066 Sandrigo VI Tel 0444 751030 r a Fax 0444 759728...

Reviews: