Installation and connection
22
TM800_D00165_00_M_XXEN/06.2015
4.1.4
Installing the flush-mounting enclosure with mounting frame (UPE)
The front plates are fitted into the wall-mounting enclosure and identified by a number identical to
the number of the enclosure. The front plate number must be identical to the enclosure number!
Note: Do not remove the plaster cover during the installation to protect the wall-mounting enclo-
sure!
1. Before inserting the cables remove the knockouts. Lead the power supply cables into the
enclosure.
2. Install the mounting frame and the wall-mounting enclosure (UPE) deeper than the finished
wall surface (i.e. tile thickness plus adhesive thickness). Note: The wall-mounting enclosure is
partially covered by the wall surface (e.g. tile)
3. Once the enclosure is firmly installed and the joints are filled, the plaster cover can be
removed.
Size of the panel and flush-mounting enclosure
Typical tile grid
150 mm tile grid= 147 mm tile + 3 mm joint
153 mm tile grid= 150 mm tile + 3 mm joint
Calculation of the panel size
Panel dimension
= number of tiles x tile grid - one joint width
Example:
Panel dimension
= 2 x 150 mm - 3 mm
Panel dimension
= 297 mm
Calculation of the flush-mounting enclosure size
Flush-mounting enclosure dimension= Number of tiles x tile grid - one joint width + 10 mm
Example:
Flush-mounting enclosure dimension= 2 x 150 mm - 3 mm + 10 mm
Flush-mounting enclosure dimension= 307 mm