Internal components and modules
88
TM800_D00165_00_M_XXEN/06.2015
Outputs BMI8/4 a
Switching elements ..................................................................................... 4 changeover contacts (AC 250 V, 5 A (AC1)
Operating principle ................................................................................. N/C operation or N/O operation programmable
Electrical service life under rated operating conditions ........................................................10,000 switching operations
Contact data acc. to IEC 60947-5-1
Utilisation category ..................................................... AC-13 ............. AC-14 ............. DC-12 ............. DC-12 ........ DC-12
Rated operational voltage...............230 V 230 V 24 V 110 V 220 V
Rated operational current ............................................. 5 A ................. 3 A ..................1 A ................. 0.2 A ........... 0.1 A
Minimum contact rating................................................................................................................. 1 mA at AC/DC > 10 V
Connections inputs/outputs
Cable length per connection..................................................................................................................................≤ 500 m
Wire cross section at least ................................................................................................................................... 0.75 mm²