Technical data
Technical data
iso685-x-B_D00177_07_M_XXEN/07.2019
66
Environment/EMC and temperature ranges
EMC ................................................................................................................................................................................. IEC 61326-2-4
5)
Operating temperature........................................................................................................................................................ -25…+55 °C
Transport.............................................................................................................................................................................. -40…+85 °C
Long-term storage .............................................................................................................................................................. -40…+70 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)............................................................................ 3K5 (no condensation and formation of ice possible)
Transport (IEC 60721-3-2) ................................................................................................................................................................ 2K11
Long-term storage (IEC 60721-3-1) ................................................................................................................................................. 1K22
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)...........................................................................................................................................................3M4
Transport (IEC 60721-3-2)...................................................................................................................................................................2M4
Long-term storage (IEC 60721-3-1) .................................................................................................................................................1M12
Area of application ............................................................................................................................................................... ≤ 3000 m NN
Connection
Connection type...................................................................................................pluggable screw-type terminal or push-wire terminal
Screw-type terminals:
Nominal current............................................................................................................................................................................... ≤ 10 A
Tightening torque.......................................................................................................................................... 0.5…0.6 Nm (5…7 lb-in)
Conductor sizes.........................................................................................................................................................................AWG 24-12
Stripping length................................................................................................................................................................................. 7 mm
rigid/flexible .......................................................................................................................................................................0.2…2.5 mm²
flexible with ferrule, with/without plastic sleeve............................................................................................................0.25…2.5 mm²
Multiple conductor, rigid.......................................................................................................................................................0.2…1 mm²
Multiple conductor, flexible ...............................................................................................................................................0.2…1.5 mm²
Multiple conductor, flexible with ferrule without plastic sleeve .......................................................................................0.25…1 mm²
Multiple conductor, flexible with TWIN ferrule with plastic sleeve..................................................................................0.5…1.5 mm²
Push-wire terminals:
Nominal current............................................................................................................................................................................... ≤ 10 A
Conductor sizes.........................................................................................................................................................................AWG 24-12
Stripping length............................................................................................................................................................................... 10 mm
rigid/flexible .......................................................................................................................................................................0.2…2.5 mm²
flexible with ferrule, with/without plastic sleeve............................................................................................................0.25…2.5 mm²
Multiple conductor, flexible with TWIN ferrule with plastic sleeve..................................................................................0.5…1.5 mm²
Push-wire terminals X1:
Nominal current................................................................................................................................................................................. ≤ 8 A
Conductor sizes.........................................................................................................................................................................AWG 24-16
Stripping length............................................................................................................................................................................... 10 mm
rigid/flexible .......................................................................................................................................................................0.2…1.5 mm²
flexible with ferrule without plastic sleeve......................................................................................................................0.25…1.5 mm²
flexible with TWIN ferrule with plastic sleeve ...............................................................................................................0.25…0.75 mm²
Other
Operating mode........................................................................................................................................................continuous operation
Mounting position (0°)...........................................................................display-oriented, cooling slots must be ventilated vertically
6)
Degree of protection internal components .........................................................................................................................................IP40
Degree of protection terminals ............................................................................................................................................................IP20
DIN rail mounting acc. to............................................................................................................................................................ IEC 60715
Screw fixing...................................................................................................................................................... 3 x M4 with mounting clip
Enclosure material ............................................................................................................................................................... polycarbonate
Flammability class .................................................................................................................................................................................V-0
ANSI code ............................................................................................................................................................................................... 64
Dimensions (W x H x D)............................................................................................................................................... 108 x 93 x 110 mm
Weight ........................................................................................................................................................................................... < 390 g
1)
At a frequency > 200 Hz, the connection of X1 and remote must be insulated. Only permanently installed devices which at least
have overvoltage category CAT2 (300 V) may be connected.
2)
Indication limited outside the temperature range -25…+55 °C.
3)
U
s
[Volt] = supply voltage ISOMETER®
4)
Only for
U
n
≥ 50 V.
5)
This is a class A product. In a domestic environment, this product may cause radio interference. In this case, the user may be re-
quired to take corrective actions.
6)
Recommendation: Mounting position 0° (display-oriented, cooling slots must be ventilated vertically).
At mounting position 45°, the max. operating temperature is reduced by 10 °C.
At mounting position 90°, the max. operating temperature is reduced by 20 °C.
"W" option data deviating from the standard version
Devices with the suffix "W“ feature increased shock and vibration resistance. The electronics is covered with a special varnish to pro-
vide increased protection against mechanical stress and moisture. (Refer the following information box)
Rated operational current switching elements. ........................................................................................max. 3 A (for UL applications)
Ambient temperatures:
Operating temperature .......................................................................................................................................................-40…+70 °C
........................................................................................................................................................... -40…+65 °C (for UL applications)
Transport..............................................................................................................................................................................-40…+85 °C
Long-term storage...............................................................................................................................................................-40…+70 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................................... K5 (condensation and formation of ice possible)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .......................................................................................................................................................... 3M7
Combination of ISOMETER® sensor variant with an FP200W:
The requirements of the "W" option will only be fulfilled if the ISOMETER® sensor variant is mounted on
DIN rail and connected to the FP200W via the patch cable.
Refer also to the quick-start guide FP200 (document number D00169).