Settings
Settings
iso685-x-B_D00177_07_M_XXEN/07.2019
31
9.2
(1.3) Profile
Adapt the area of application of the ISOMETER® to your system profile. For a description
of the profiles, refer to chapter „Technical data“.
The following can be selected:
9.2
(1.4) System type
Adapt the ISOMETER® to the IT system to be monitored. The following can be selected:
9.2
(1.5) Coupling
Adapt the ISOMETER® to the requirements of Bender coupling devices. For a description
about the connection of coupling devices refer to chapter “Coupling devices” .
You may select.
9.2
(1.6) ISOnet
Make the settings to use the ISONet function.
The ISOnet function ensures via the Ethernet connection that
only
one
ISOMETER® of the
interconnection is active when several ISOMETER®s are connected to an IT system.
For further information regarding the ISOnet function, refer to the chapter „Special func-
tions for couppled IT systems“.
•Power circuits
Suitable for most IT systems.
•Control circuits
Not recommended for voltages > 230 V.
•Generator
Fast measuring times, fast fault location possible.
•High capacitance
Suitable for systems with high system leakage capacitances.
•Inverter > 10 Hz
Suitable for systems with dynamic frequency control by inverters
in the range 10…460 Hz.
•Inverter < 10 Hz
Suitable for systems with extremely low frequency controls in the
range 0.1…460 Hz.
•Customer-specific
Enables the Bender service to make customer-specific settings.
•DC
DC system
•AC
Single-phase AC system
•3AC
3AC system
•none
•AGH150W
•AGH204S-AK80
•AGH204S-AK160
•AGH520S
•AGH676S-4
9.2
(1.6.1) ISOnet
Activate or deactivate the ISONet function
9.2
(1.6.2) Number of devices
Configure the number of devices (2…20) in a subsystem.
9.2
(1.7) ISOloop
Schalten Sie die ISOloop-Funktion aktiv oder inaktiv:
9.2
(1.7.1) ISOloop
Turns the function on or off.
9.2
(1.7.2) Measured value subscription
When the measured value subscription and the ISOloop function are activated, the mea-
sured values of the active measuring device are distributed within the team and shown
on all displays.
9.2
(1.8) (Start)
The ISOMETER® can be operated with a start-up delay of 0…600 seconds. The start-up is
delayed until the initial measurement takes place.
9.2
(1.9) Coupling monitoring
The ISOMETER® continuously monitors the coupling of energised systems. The coupling
of de-energised systems is monitored at 8-hour intervals. This monitoring function can be
activated or deactivated.
9.2
(1.10) Inputs
The ISOMETER® provides a total of three digital inputs.
•off
The ISOnet is deactivated
•BCOM
The ISOnet function is activated via BCOM
1. ISOloop:
2. Measured value subscription:
•on
Coupling monitoring is activated.
•off
Coupling monitoring is deactivated.