Alarm messages
iso685-x-B_D00177_07_M_XXEN/07.2019
59
13.4 ISOloop
These messages only become active after activating the ISOloop function.
Alarm message
Description
Measures
LED indicators
ISOloop configuration is not
uniform!
The ISOloop group configuration is not uniform for all
devices in the group or one of the devices has no configura-
tion
• Make sure that all devices in the group to be configured
are able to communicate (correctly set and BCOM and
Ethernet connection established).
• Afterwards, upload ISOloop configuration to a device via
the web server
ISOloop configuration is
faulty!
Addresses of the group configuration (system-subsystem-
device address) do not match the addresses on the devices
in this group
• see above
The ISOloop configuration
was not found!
There is no ISOloop configuration on this device
• see above
Error while distributing the
ISOloop configuration!
The ISOloop configuration could not be distributed to all
devices (devices were not switched on or faulty BCOM con-
nection) OR function was not activated when uploading the
configuration file OR function was not activated on all
devices during upload
• see above