Device communication
70
isoxx1685Dx-x25_D00272_07_M_XXEN/09.2022
9.1.7
Alarm and operating messages via the BMS bus
Messages are transmitted to a maximum of 12 BMS channels. All alarm and operating messa-
ges that may occur are described below.
9.1.7.1 Alarm messages
9.1.7.2 Operating messages
Alarm
Channel
Description
Alarm 1 (insulation fault)
1
Insulation resistance "Prewarning"
(Value < response value 1,
R
F
<
R
an1
)
Alarm 2 (insulation fault)
2
Insulation resistance "Alarm"
(Value < response value 2,
R
F
<
R
an2
)
System connection
4
Connection fault system
Connection PE
5
Connection fault earth
Device error
7
Internal device error
Start insulation fault location
(isoxx1685DP only)
9
The insulation fault location is started
Overtemperature coupling
10
Overtemperature coupling terminal L1/+
Overtemperature coupling
11
Overtemperature coupling terminal L2/–
Overtemperature PGH
(isoxx1685DP only)
12
Overtemperature of the locating current injector
Alarm
Channel
Description
Insulation resistance
1
Current insulation resistance
R
F
(when
R
F
> (
R
an1
+ hysteresis))
Insulation resistance
2
Current insulation resistance
R
F
(when
R
F
> (
R
an2
+ hysteresis))
Leakage capacitance
4
Leakage capacitance
C
e
in nF, μF
Mains voltage
5
Current system voltage
U
N
Partial voltage U+/PE
6
Current partial voltage terminal L1/+ to earth
Partial voltage U-/PE
7
Current partial voltage terminal L2/– to earth
PGH current
(isoxx1685DP only)
8
Current PGH locating current (when EDS system is
active)
Temperature coupling
10
Current temperature of the coupling L1/+
Temperature coupling
11
Current temperature of the coupling L2/–
Temperature PGH
(isoxx1685DP only)
12
Current temperature of the locating current injector