Operation and setting
63
IRDH575_D00089_05_M_XXEN/01.2020
6.6.5
K3 alarm: ON
The K3 relay can be used either for one or for two functions. It is always used
for signalling IRDH575 device errors.
K3 alarm: on
= K3 signals additionally occurring EDS alarms as common alarm.
Please note that this function is only active in the master mode
(BMS address 1 = factory setting).
K3 alarm: off
= K3 only signals IRDH575 device
Detailed information about the function is given on page 28 and page 26.
6.7
EDS460/490 menu
This menu can only be opened in the master mode (bus address 1), all the set-
tings via the BMS bus can only be carried out in the master mode, even when
several IRDH575 are interconnected. After starting the menu, the IRDH575
queries the essential parameters of EDS46… / EDS49… and the current para-
meters appear on the display.
6.7.1
General
The following parameters have an effect on that device the BMS address of
which is being displayed. Set the address in order to select the appropriate de-
vice.
Memory
Use this menu option to switch the fault memory of the selected EDS46…/
EDS49… on or off. Factory setting = off.
Trigger
Use this parameter to specify whether the fault location of EDS46… / EDS49…
is to be started by an IRDH575 (Com) or if automatically and continuously all
measuring channels are measured in parallel (Auto). Factory setting = Com.