Function
27
IRDH575_D00089_05_M_XXEN/01.2020
Behaviour of the analogue output
Setting
Manual test
Automatic test
0-20 mA
20 mA
while test procedure
0 mA
The current value depends
on the insulation value
4-20 mA
20 mA
while test procedure
4 mA
The current value depends
on the insulation value
Error
message
Meaning
Steps to taken
System
connection?
No low-resistance
connection of
terminals L1, L2, L3
to the system
1. Check the wiring of termi-
nal L1, L2, L3 to the system
2. Press the TEST button
3. Switch the supply voltage
on and off
4. Check the fuses
Connection
PE?
No low-resistance
connection of the
terminals
and
KE to earth (PE)
1. Check wiring of terminal
and KE to earth (PE)
2. Press the TEST button
3. Switch the supply voltage
on and off
Device error x
Internal device
error
1. Press the TEST button
2. Switch the supply voltage
on and off
3. Please contact Bender