8. Werkseinstellungen
Menü
Untermenü
Werkseinstellung
1. EXIT
2. HISTORY INFO
3. ISO SETUP
1. Exit
2. Alarm1:
40 kΩ
3. Alarm2:
10 kΩ
4. K1:
N.O Test
5. K2:
N.O Test
6. Memory:
off
7. M+/M-:*
0-20 mA*
4. ISO ADVANCED
1. Exit
2. AGH:
no
3. Ce. max:
150 μF
4. Measure:
AMP
5. Autotest:
24 h
6. Clock:*
MEZ (HH:MM)*
7. Date:*
Aktuelles Datum
(TT:MM:JJJJ)*
8. Test:*
12:00*
5. COM SETUP*
1. Exit*
2. Addr:*
3 (Slave)*
3. ISOnet:*
off*
4. ISO Monitor:*
6. PASSWORD
1. Exit
2. Password:
000