Technical data IRDH275(B)
76
IRDH275_D00122_03_M_XXEN/05.2017
Measuring circuit
Measuring voltage
U
m
........................................................................................................................................ ≤ 50 V
Measuring current
I
m
max. (at
R
F
= 0 Ω)...................................................................................................... ≤ 280 μA
Internal DC resistance
R
i
.................................................................................................................................. ≥
180 kΩ
Internal impedance
Z
i
at50 Hz......................................................................................................................... ≥ 180 kΩ
Permissible extraneous DC voltage
U
fg
.................................................................................................... ≤ DC 1200 V
Permissible system leakage capacitance
C
e
................................................................................................... ≤500 μF
Factory setting....................................................................................................................................................... 150 μF
Displays
Display, illuminated .............................................................................................................................. two-line display
Characters (number of characters)........................................................................................................................2 x 16
Display range, measuring value ............................................................................................................. 1 kΩ…10 MΩ
Operating uncertainty (20 kΩ…1 MΩ) (acc. to IEC 61557-8:2007-01) .................................................... ±15 % **
Operating uncertainty (1 kΩ…20 kΩ) .......................................................................................... ±1 kΩ
/
±15 % **
Operating uncertainty (1 MΩ…10 MΩ) .................................................................................. ±0.1 MΩ / ±15 % **
** = under test conditions according to IEC 61326-2-4, the tolerances may double
Outputs/inputs
TEST/ RESET button..............................................................................................................................internal /external
Cable length TEST/RESET button external ......................................................................................................... ≤ 10 m
Current output for measuring instrument SKMP (scale centre point = 120 kΩ): ..........................................................
Current output IRDH275 (load) ...................................................................................................... 400 μA (≤ 12.5 kΩ)
Current output IRDH275B (load) .........................................................................................................20 mA (≤ 500 Ω)
Accuracy current output (1 kΩ…1 MΩ)
in relation to the displayed measured value........................................................................................ ±10 %, ±1 kΩ
Serial interface
Interface / Protocol IRDH275 ....................................................................................................... RS485 / ASCII-IsoData
Interface / Protocol IRDH275B.................................................................................................................... RS485 / BMS
Connection ................................................................................................................................................ terminals A/B
Cable length ................................................................................................................................................... ≤ 1200 m
Shielded cable (shield on one side to PE) ................................................ two-core, ≥ 0.6 mm
2
, e.g. J-Y(St)Y 2 x 0.6
Terminating resistor.................................................................................................................................. 120 Ω (0.5 W)
Device address, BMS bus .................................................................................................. 1…30 (factory setting = 3)
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...