Function
25
IRDH275_D00122_03_M_XXEN/05.2017
Function input F1/F2 for connection or disconnection of
IT systems being monitored
The ISOMETER® can be disconnected from the IT system and set to STANDBY
mode with the function input F1/F2. If the input F1/F2 is bridged, the connec-
tions L1/L2 are switched off via internal coupling relays, the measuring func-
tion is stopped and the message "STANDBY" appears on the display. Software
version 1.4 or higher does not indicate the measured insulation resistance
during the disconnection, but indicates the value > 10 MΩ. Furthermore, the
alarm relays and alarm LEDs no longer provide alarm messages. After opening
the function input F1/F2, the connection to the IT system will be restored and
a completely new measuring cycle for insulation monitoring is started.
With this function, selective disconnection of an IRDH275B in interconnected
IT systems can be carried out via auxiliary contacts of the respective coupling
switch. One coupling switch each in a line-type or ring-type arrangement can
deactivate a subsequent IRDH275B. This arrangement guarantees that only
one ISOMETER® is active in each galvanically connected system. In a ring-type
arrangement with all coupling switches closed, it can be assumed that all
ISOMETER®s are deactivated. In order to prevent this, a BMS Master (IRDH275B
BMS address 1) monitors the condition of the function input F1/F2 of all slave
ISOMETER®s.
When all slave ISOMETER®s are in the STANDBY mode, the insulation monitor-
ing function of the Master ISOMETER® and hence the function input F1/F2 of
the Master are without function in this mode.
Details are shown in the graphic below.
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...