Function
22
IRDH275_D00122_03_M_XXEN/05.2017
When a device error or connection fault is found, the message "!Error!" ap-
pears on the display, the device fault LED lights up, the relay K2 (21-22-24)
switches and the respective fault message (see table) is indicated. If such a de-
vice fault occurs, a self test is started again every minute. If no more malfunc-
tion is detected, the fault message is deleted automatically and the device
fault LED extinguishes.
During operation, the self test function can be started by pressing the TEST
button (internal or external). The self test can also be started automatically
every hour or every 24 hours by selecting "ISO ADVANCED: Autotest" menu.
The alarm relays Alarm1/2 only switch after starting the self test function by
pressing the TEST button, that means if an automatic self test has been select-
ed, the alarm relays do not switch.
Behaviour of the analogue output
Setting
Manual test
Automatic test
0-20 mA
20 mA
while test procedure
0 mA
The current value depends
on the insulation value
4-20 mA
20 mA
while test procedure
4 mA
The current value depends
on the insulation value
Summary of Contents for ISOMETER IRDH275
Page 36: ...Anschluss 36 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 40: ...Inbetriebnahme Schema dreiteilig 40 IRDH275_D00122_03_M_XXDE 05 2017 ...
Page 91: ...91 IRDH275_D00122_03_M_XXDE 05 2017 W Werkseinstellungen 73 Z Zulassungen 79 ...
Page 128: ...Connection 36 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 132: ...Commissioning flow chart threepart 40 IRDH275_D00122_03_M_XXEN 05 2017 ...
Page 144: ...Operation and setting 52 IRDH275_D00122_03_M_XXEN 05 2017 Diagram ISO SETUP ...
Page 152: ...Operation and setting 60 IRDH275_D00122_03_M_XXEN 05 2017 6 6 4 Diagram COM SETUP IRDH275B ...
Page 154: ...Operation and setting 62 IRDH275_D00122_03_M_XXEN 05 2017 6 7 2 Diagram PASSWORD ...