![Bender EDS3090 Manual Download Page 56](http://html1.mh-extra.com/html/bender/eds3090/eds3090_manual_2731604056.webp)
Technical specifications
56
EDS309x_D00012_03_M_XXEN/11.2014
7.5 Technical specifications AGE185
Insulation co-ordination according to IEC 60664-1
Rated insulation voltage ...................................................................................................................................................................................... AC 1000 V
Rated impulse voltage/degree of pollution ............................................................................................................................................................... 4 kV/3
Nominal system voltage
U
n
.......................................................................................................... 3AC/AC 42…460 Hz, 500…790 V, DC 400…960 V
Other
Degree of protection of built-in components DIN EN 60529 (VDE 0470-1) ................................................................................................................ IP30
Connection type/wire: ................................................................................... Safety laboratory connectors with green-yellow connection wire 1 mm
2
Weight ..................................................................................................................................................................................................................... ≤ 200 g
Dimensions WxHxD: ............................................................................................................................................................................... 88.5 x 42 x 21 mm
7.6 Standards
Observe the applicable national and international standards. The series EDS309…
complies with the standards:
DIN VDE 0100-410 (VDE 0100-410)
Low-voltage electrical installations – Part 4-41:
Protection for safety – Protection against electric shock (IEC 60364-4-41, modified);
German version HD 60364-4-41
DIN EN 61557-9
Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. –
Equipment for testing, measuring or monitoring of protective measures - Part 9:
Equipment for insulation fault location in IT systems (IEC 61557-9);
German version EN 61557-9
DIN EN 61010-1; VDE 0411-1
Safety requirements for electrical equipment for measurement, control and laboratory use –
Part 1: General requirements (IEC 61010-1);
German version EN 61010-1
Summary of Contents for EDS3090
Page 6: ...Table of Contents 6 EDS309x_D00012_03_M_XXEN 11 2014...
Page 26: ...Considerations prior to use 26 EDS309x_D00012_03_M_XXEN 11 2014...
Page 62: ...Frequently Asked Questions 62 EDS309x_D00012_03_M_XXEN 11 2014...
Page 65: ......
Page 66: ......
Page 67: ......