![Bender EDS3090 Manual Download Page 51](http://html1.mh-extra.com/html/bender/eds3090/eds3090_manual_2731604051.webp)
Operation
51
EDS309x_D00012_03_M_XXEN/11.2014
6.13 Coupling device AGE185 for higher system voltages
This option is available for the variants EDS3090PG, EDS3090PG-13 and EDS3096PG with the locat-
ing current injectors PGH185 and PGH186. The coupling device AGE185 expands the nominal volt-
age range of the insulation fault location system EDS309…
The AGE185 reduces the losses in the locating current injector PGH18… As a result it makes it possi-
ble to connect the PGH18… to nominal system voltages up to AC 790 V or DC 960 V.
Assembly, connection and placing in operation
Connection and placing in operation only by an electrical technician!
It is imperative the existing safety regulations are followed!
The ends of the wires from the AGE185 can be connected, as necessary and to suit the local situation,
to the system's PE terminal and the PE socket on the PGH186; it is not necessary to take into account
the polarity.
Connection diagram
Abb. 6.3: Connection diagram EDS309… with AGE185
Risk of electric shock!
On touching live uninsulated conductors, death or serious injury may be caused.
For this reason avoid any contact whatsoever with active conductors on con-
necting the PGH or the AGE.
DANGER
PGH186
100mA
10 mA
25 mA
Imax
ON
ON
Us
L1(+)
L2(-)
L3
AC/DC
PE
IT System
AGE185
PGH186
EDS195P
U
s
T
o
the loads
PSA3052
MESSZANGE / CLAMP
ON PROBE
Datenblatt / Da
tasheet :
TGH13xx
Durchmesser / Diameter : 52 mm
Art.-N
r.
/
Art.-no. : B 980 6xx
EDS195P
ISOSCAN®
I L
I n
ALARM
I n
I L
INFO
MENU
HOLD
RESET
ESC
OK
Summary of Contents for EDS3090
Page 6: ...Table of Contents 6 EDS309x_D00012_03_M_XXEN 11 2014...
Page 26: ...Considerations prior to use 26 EDS309x_D00012_03_M_XXEN 11 2014...
Page 62: ...Frequently Asked Questions 62 EDS309x_D00012_03_M_XXEN 11 2014...
Page 65: ......
Page 66: ......
Page 67: ......