![Bender EDS3090 Manual Download Page 36](http://html1.mh-extra.com/html/bender/eds3090/eds3090_manual_2731604036.webp)
Operation
36
EDS309x_D00012_03_M_XXEN/11.2014
6.6.7
Significance of the display elements
The elements shown relate to the EDS mode (I
Δ
L
). This mode is used for insulation fault location.
6.7 Standard displays on the EDS195P
6.7.1
EDS measurement (
I
Δ
L
)
6.7.1.1
Standard display if there is no cable to be measured in the clamp
The device is in the EDS mode (
I
Δ
L
).
A measured locating current
I
Δ
L
is not indicated, as there is no conductor in the measuring clamp.
The display shows the timer count (29…0).
1
Indication of the locating current pulse:
= Positive pulse,
= Pause or no measurement possible when permanently displayed
= Negative pulse
29
= Timer (29…0) shows the duration of a measurement of an outgoing
circuit
2
Indication of the selected transformer type:
-
PSA30xx
= PSA30… / PSA3165
(suitable for
I
Lmax
= 50 mA)
-
W/WR/WS
= W…. / WR…. / WS….
(suitable for
I
Lmax
= 50 mA)
-
PSA33xx
= PSA33…
(suitable for
I
Lmax
= 5 mA)
-
W/WS-8000
= W….-8000 / WS….-8000 (suitable for
I
Lmax
= 5 mA)
-
WF
= WF….
(only suitable for
I
Δ
n
)
3
H = Hold function is activated; measured value indication "frozen"
4
M = Fault memory is activated
5
Loudspeaker symbol visible:
The presence of an alarm is also output audibly
6
Charge state of the rechargeable battery in the steps 0%, 33%, 66%,100%
7
Resp. = Response value I
Δ
L
8
I
Δ
L
= Indication of the actual locating current measured
I
L
= 8mA
Resp. = 5mA
M H
PSA30xx
1
2
3
4
5
7
8
6
I
L
= mA
Anspr. = 5mA
M
PSA30xx
29