Pre-Installation Requirements
6. 2
Support Requirements
Prior to installation, ensure the proper structural support will be used. Mini-
mum load bearing requirements are listed in the table below. For panels
weighing in excess of 500 lb (230 kg), install both horizontal (bottom) and ver-
tical (side) supports.
6. 3
Size Requirements
Verify backbox dimensions on label. Ensure the wall space required is available
before proceeding with backbox installation. Ensure the mounting style (sur-
face or flush) is correct for the application. For reference, standard backbox
sizes are listed in the table below. Dimensions are given in inches (cm).
NOTE:
Custom configurations may have special
weight and load bearing requirements.
Type
Weight (lb)
Weight (kg)
MIP series
370
168
MIE series
650
295
MIC series
650
295
MID series
675
306
MIX series
700
317
Model
Height
Width
Depth
B662406(S)
66” (167.6 cm)
24” (61 cm)
6” (15.2 cm)
B662408(S)
66” (167.6 cm)
24” (61 cm)
8” (20.3 cm)
B723012(S)
72” (182.9 cm)
30” (76.2 cm)
12” (30.5 cm)
B723014(S)
72” (182.9 cm)
30” (76.2 cm)
14” (35.6 cm)
B803608(S)
80” (203.2 cm)
36” (91.4 cm)
8” (20.3 cm)
Summary of Contents for B662406
Page 1: ...Isolated Power Panels For Healthcare Facilities NAE209501 2 02 2019 T M EN Manual...
Page 21: ...Installation 21 IP Panels 2018 Bender Inc All Rights Reserved...
Page 34: ...34 IP Panels 2018 Bender Inc All Rights Reserved Installation 7 9 2 MIC Series...
Page 35: ...Installation 35 IP Panels 2018 Bender Inc All Rights Reserved 7 9 3 MID Series...
Page 43: ......