Components
11
IP Panels © 2018 Bender Inc. All Rights Reserved
4. 2
Front Trim Package
The front trim is manufactured from a minimum
14 GA, type 304 stainless steel. It contains a door
with hidden hinges and flush mounted key lock.
The door provides access to circuit breakers and
optional fault location (EDS) accessories if
equipped. Most front trims are provided with
provisions for future field installation of recepta-
cle and/or fault location assembly kits.
Front trims may be used with flush-mounted or
surface-mounted backboxes. For flush mounted
panels, the front trim extends 1” (25.4 mm) on
all sides of the backbox. For surface-mounted
panels, the front trim has the same height and
width as the backbox.
4. 3
Isolation Transformer Kit
The isolation transformer kit contains the fol-
lowing:
•
Transformer and mounting hardware
•
Primary main circuit breaker and bracket
assembly
•
Secondary main circuit breakers (where
applicable)
•
Breaker sub-plate and mounting hardware
Isolation transformers used in isolated power
systems are special-purpose, low-voltage, dry-
type transformers. They are application-specifi-
cally designed and fulfill the requirements of UL
5085 and UL 1047.
The primary main breaker, mounting hardware,
and sub-plate are included in the isolation trans-
former kit. For MID series panels (and custom
configurations where applicable), the isolation
transformer kit will also include secondary main
circuit breakers.
Summary of Contents for B662406
Page 1: ...Isolated Power Panels For Healthcare Facilities NAE209501 2 02 2019 T M EN Manual...
Page 21: ...Installation 21 IP Panels 2018 Bender Inc All Rights Reserved...
Page 34: ...34 IP Panels 2018 Bender Inc All Rights Reserved Installation 7 9 2 MIC Series...
Page 35: ...Installation 35 IP Panels 2018 Bender Inc All Rights Reserved 7 9 3 MID Series...
Page 43: ......