2 GFGC_D00395_00_D_XXEN/05.2019 

Ground Fault and Ground Continuity 
Protection Panel GFGC

Protection Panel GFGC

Device features

•  Universal voltage selection between 120 

and 600 V

•  Features ground fault detection, ground 

integrity monitoring, and power inter-

ruption in case of alarm

•  Predefined settings from factory
•  6 mA ground fault trip level
•  Inverse time curve for interrupting cir-

cuit on a ground fault

•  Adjustable ground continuity trip level 

between 0.1 Ω…100 Ω (preset to 3 Ω)

•  NEMA 12 painted steel enclosure
•  External test and reset buttons
•  External LED indication for power and 

ground fault/ground integrity alarms

•  Internal real-time indications of ground 

fault current and ground integrity via  

digital displays 

Product description

The GFGC series of panels is an all-in-one solution for ground fault detection, ground 

continuity monitoring, and power interruption in case of an alarm. Utilizing the latest in 

technology, the GFGC panels can detect ground fault currents down to 6 mA without the 

problems associated with high sensitivity nuissance tripping. The GFGC unit also verifies 

ground connection integrity over a widely adjustable range. The universal voltage selection 

allows use of this panel on systems from 120 VAC to 600 VAC. 30 A, 60 A, and 100 A units 

are available.
Bender LifeGuard GFGC protection panels are Listed Enclosed Industrial Control Panels 

certified to UL 508A.
Ground fault detection: The internal ground fault detector RCMA421H extends the capa-

bility of standard ground fault monitors to detect ground fault current in both AC and DC 

systems, as well as through all stages of power conversion, such as with variable frequency 

drives. The RCMA421H combines a trip level of 6 mA with protection against nuissance 

tripping through operation on an inverse time curve (per UL943, the standard for personnel 

protection), as well as exceptional noise filtering.
Open ground detection: The internal ground continuity monitor GM420 adds an additional 

layer of protection by continuously monitoring the integrity of the ground conductor 

line. A wide adjustable range from 0.1 Ω to 100 Ω ensures the proper level of protection 

for nearly every application. In addition, the GM420 monitors for extraneous voltages be-

tween its connection points.

Applications

•  Loading docks
•  Fueling stations
•  Systems requiring frequent user connections/disconnections

Function

The GFGC series of panels is designed to interrupt power to a circuit when either a ground 

fault or an open ground is detected. The entire solution is contained inside a NEMA 4 

painted steel enclosure. Light indicators as well test/reset buttons on the front of the  

enclosure allow for functionality without requiring access inside the panel. Settings are 

preset; only a simple internal wiring is required.
When a ground fault is detected, the contactor will trip the main circuit based on an inverse 

time curve (per UL943) relative to the preset 6 mA value. The inverse time curve assists in 

alleviating potential nuissance tripping issues.
If an open ground is detected, the same contactor will trip the main circuit. The ground 

continuity monitor utilizes a ground connection, as well as a field pilot wire connection 

on the exterior of the enclosure. This connection is required for proper operation. The 

open ground monitor will not allow the contactor to remain pulled in without a proper 

field connection.

Universal Voltage 120…600 V

for Grounded AC Systems

Device adjustability and preset values

Type

Adjustability

Preset defaults

Ground fault, trip value

6 mA, fixed

6 mA

Ground fault, time delay

Inverse time curve

Inverse time curve

Open ground, trip value

0.1…100 

Ω

Ω

Open ground, time delay

0…99 s

0 s

Summary of Contents for B541300044

Page 1: ...GFGC_D00395_00_D_XXEN 05 2019 GFGC Protection Panel Universal Ground Fault and Ground Continuity Panel For 120 VAC to 600 VAC Grounded Systems BENDER Group...

Page 2: ...ance tripping through operation on an inverse time curve per UL943 the standard for personnel protection as well as exceptional noise filtering Open ground detection The internal ground continuity mon...

Page 3: ...ation The green POWER ON lamp illuminates when power is available to the load The red CIRCUIT TRIPPED lamp illuminates when power is removed from the load If unit has tripped clear the fault and press...

Page 4: ...6 7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 208 V Pilot Wire Connection On exterior of enclosur...

Page 5: ...7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 480 V Pilot Wire Connection On exterior of enclosure T...

Page 6: ...the connector on the outside of the enclosure There is a proper connection between the clamp and the ve hicle object There are no broken ground connections in the system being protected The panel must...

Page 7: ...13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220 V Rated operational current 5 A 3 A 1 A 0 2 A 0 1 A Minimum contact load 1 mA at AC DC 10 V Fault memory behavior Latch...

Page 8: ...life under rated operating conditions 10 000 switching cycles Contact data acc to IEC 60947 5 1 Utilization category AC 13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220...

Page 9: ...Dimensions GFGC 60 and GFGC 100 enclosure 12 12 12 6 6 12 16 12 12 6 16 6 Ordering Information Load Ampere Rating Mfg Reference No Type Ordering Number 30 A LG30 600 120 3 4 4 PA CH XSLU GFGC 30 B541...

Page 10: ...alid until 05 2019 unless otherwise indicated USA Mexico Exton PA 800 356 4266 610 383 9200 info bender org www benderinc com Canada Mississauga ON 800 243 2438 905 602 9990 info bender ca com www ben...

Reviews: