Bender B541300044 Product Description Download Page 3

Ground Fault and Ground Continuity – Protection Panel GFGC

 

 

 GFGC_D00395_00_D_XXEN/05.2019 

3

Procedure for wiring GFGC assembly into system

•  Locate the wiring diagram specific to the line voltage. Be sure 

to select the voltage and phase type specific to the point at 

where the GFGC panel is connecting.

•  Connect the incoming lines to the contactor, being sure to have 

all phases going through the WN-35BS current transformer (in-

cluding the neutral if one exists). 

Order of conductors is im-

portant

.

   When connecting to the contactor, placement of the neutral is 

important. Connect the outgoing lines in the same manner.  

Do not pass the ground conductor through the current 

transformer or connect it to the contactor!

•  Connect the incoming and outgoing ground wires to the 

ground lug.

•  Locate the control transformer. Terminal 1 (“Com. H2”) should 

already be connected. Connect it if it is not.

•  Connect the other wire to the terminal specific to the line volt-

age being protected. For instance, if the system is a 208/120 V 

system, and the GFGC assembly is connected on the 208 V por-

tion of the circuit, connect the wire to the terminal labeled 

“208.”

•  Connect the ground pilot wire clamp to the connector on the 

outside of the enclosure.

GFGC enclosure front (drawing not to scale)

Operation

The green POWER ON lamp illuminates when power is available to the load.
The red CIRCUIT TRIPPED lamp illuminates when power is removed from the load.
If unit has tripped, clear the fault and press Reset to resume operation.

Ground Fault Test

 

 Unit must be tested at least once per month or before each use.

Press Test for >2 seconds. Unit must trip.
When unit trips a self test sequence starts. Wait >10 seconds.
Press Reset for >1 second. Unit should reset, restoring power to the load.

Ground Connection Monitor

   Connect a pilot lead to the powered-equipment

ground and the connection located on the bottom of this enclosure. Loss

of this connection will cause loss of load power and the OPEN GROUND lamp to light.

Technical support: 1-800-356-4266

E-mail: [email protected]

Push To Reset

POWER

ON

CIRCUIT

TRIPPED

OPEN

GROUND

GROUND FAULT

GROUND CHECK

GFGC

Push To Test

Push To Test Lamp

1 - 

Power ON light/Reset pushbutton 

Light illuminates when power is received to the device and not 

in an alarm state. 

Pushing the button for > 1 second resets the device.  

(Must wait for test to complete!)

2 - 

Circuit tripped light/Test pushbutton 

Light illuminates when the circuit has been tripped due to a 

ground fault. 

Pushing the button for > 2 seconds runs a test on the ground 

fault detection unit.

3 - 

Open ground light/Light test pushbutton 

Light illuminates when the ground continuity monitor has  

detected an open ground. 

Pushing the button runs a test on the open ground light.

1

2

3

Summary of Contents for B541300044

Page 1: ...GFGC_D00395_00_D_XXEN 05 2019 GFGC Protection Panel Universal Ground Fault and Ground Continuity Panel For 120 VAC to 600 VAC Grounded Systems BENDER Group...

Page 2: ...ance tripping through operation on an inverse time curve per UL943 the standard for personnel protection as well as exceptional noise filtering Open ground detection The internal ground continuity mon...

Page 3: ...ation The green POWER ON lamp illuminates when power is available to the load The red CIRCUIT TRIPPED lamp illuminates when power is removed from the load If unit has tripped clear the fault and press...

Page 4: ...6 7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 208 V Pilot Wire Connection On exterior of enclosur...

Page 5: ...7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 480 V Pilot Wire Connection On exterior of enclosure T...

Page 6: ...the connector on the outside of the enclosure There is a proper connection between the clamp and the ve hicle object There are no broken ground connections in the system being protected The panel must...

Page 7: ...13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220 V Rated operational current 5 A 3 A 1 A 0 2 A 0 1 A Minimum contact load 1 mA at AC DC 10 V Fault memory behavior Latch...

Page 8: ...life under rated operating conditions 10 000 switching cycles Contact data acc to IEC 60947 5 1 Utilization category AC 13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220...

Page 9: ...Dimensions GFGC 60 and GFGC 100 enclosure 12 12 12 6 6 12 16 12 12 6 16 6 Ordering Information Load Ampere Rating Mfg Reference No Type Ordering Number 30 A LG30 600 120 3 4 4 PA CH XSLU GFGC 30 B541...

Page 10: ...alid until 05 2019 unless otherwise indicated USA Mexico Exton PA 800 356 4266 610 383 9200 info bender org www benderinc com Canada Mississauga ON 800 243 2438 905 602 9990 info bender ca com www ben...

Reviews: