Bender B541300044 Product Description Download Page 7

Ground Fault and Ground Continuity – Protection Panel GFGC

 

 

 GFGC_D00395_00_D_XXEN/05.2019 

7

Technical data: Ground fault monitor RCMA421H-D-2 and current transformer WN-35BS

Insulation coordination acc. to IEC 60664-1/IEC 60664-3

Rated insulation voltage 

AC 250 V

Rated impulse voltage/pollution degree 

2.5 kV/3

Protective Separation (reinforced insulation) between  (A1, A2) - (k/l, T/R) - (21, 22, 24)
Voltage tests to IEC 61010-1 

2.21 kV

Supply voltage

Supply voltage 

U

S

 

AC/DC 70…300 V

Frequency range of 

U

S

 

42…460 Hz

Power consumption 

≤ 4.5 VA

Measuring circuit

External measuring current transformer 

WN-35BS

Rated voltage (current transformer) 

2.5 kV

Rated frequency 

0…150 Hz

AC/DC measuring range 

0…40 mA

Relative percentage error ( 0…20 Hz) 

-33 %…+100 %

Relative percentage error ( 20…90 Hz) 

0…- 33 %

Relative percentage error ( 90…150 Hz) 

± 17.5 %

Operating value

Rated ground fault current 

6 mA

Time behavior

Operating time 

t

ae

 per UL943 

See diagram

Starting delay 

t

 

Operating time 

t

ae

 + 3.2 s

Display and memory

Display range (measured value) 

0…40 mA

Maximum operating error ( 0…20 Hz) 

-33/+100 %/± 2 digits

Maximum operating error ( 20…90 Hz) 

0…20 %/± 2 digits

Maximum operating error (

I

Δ

 < 2 mA) 

± 7 digits

Measured value memory capacity 

Measured alarm value set

Switching elements

Number of switching elements 

1 SPDT contact

Operating principle, adjustable 

normally energized operation

Electrical service life under rated operating conditions 

10,000 switching cycles

Contact data acc. to IEC 60947-5-1

Utilization 

category 

AC-13 AC-14 DC-12 DC-12  DC-12

Rated operational voltage 

230 V  230 V 

24 V  110 V 

220 V

Rated operational current 

5 A 

3 A 

1 A  0.2 A 

0.1 A

Minimum contact load 

1 mA at AC/DC ≥ 10 V

Fault memory behavior 

Latching operation

Connections
Connection type specification for Screw terminals

Rigid/flexible conductor sizes  

AWG 24…12/24…14

Stripped length  

0.31…0.35 in (8…9 mm)

Tightening torque  

0.36…0.44 ft-lb (0.5…0.6 N-m)

Connection type specification for Push-wire terminals

Rigid/flexible conductor sizes 

AWG 24…14

Flexible with core end sleeve 

AWG 24…16

Stripped length 

0.39 in (10 mm)

Opening force 

11.2 lb (50 N)

Test opening, diameter 

0.1 in (2.1 mm)

Environment/EMC

EMC 

acc. to UL 943

Operating temperature 

- 31…+ 150 °F (- 35…+ 66 °C)

Climatic class acc. to IEC 60721

Stationary use (IEC 60721-3-3) 

3K5 (except condensation and formation of ice)

Transport (IEC 60721-3-2) 

2K3 (except condensation and formation of ice)

Long-time storage (IEC 60721-3-1) 

1K4 (except condensation and formation of ice)

Classification of mechanical conditions IEC 60721

Stationary use (IEC 60721-3-3) 

3M4

Transport (IEC 60721-3-2) 

2M2

Long-time storage (IEC 60721-3-1) 

1M3

General data

Operating mode 

continuous duty

Position of normal use 

display-oriented

Protection class, internal components (IEC 60529) 

IP30, NEMA 1

Protection class, terminals (IEC 60529) 

IP20, NEMA 1

Enclosure material 

polycarbonate

Screw mounting 

2 x M4

DIN rail mounting acc. to 

IEC 60715

Flammability class 

UL94V-0

Documentation number 

D00395

Weight:  
 

 RCMA421H 

≤ 0.33 lb (150 g) 

WN-35BS 

≤ 0.78 lb (355 g)

Inverse time curve operation (including contactor) per UL943

260

220

240

200

180

160

140

120

100

80

60

40

20

0

0,01

0,10

1,00

10,00

T/s

I/mA

6; 5,594

30; 0,560

264; 0,0250

Summary of Contents for B541300044

Page 1: ...GFGC_D00395_00_D_XXEN 05 2019 GFGC Protection Panel Universal Ground Fault and Ground Continuity Panel For 120 VAC to 600 VAC Grounded Systems BENDER Group...

Page 2: ...ance tripping through operation on an inverse time curve per UL943 the standard for personnel protection as well as exceptional noise filtering Open ground detection The internal ground continuity mon...

Page 3: ...ation The green POWER ON lamp illuminates when power is available to the load The red CIRCUIT TRIPPED lamp illuminates when power is removed from the load If unit has tripped clear the fault and press...

Page 4: ...6 7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 208 V Pilot Wire Connection On exterior of enclosur...

Page 5: ...7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 480 V Pilot Wire Connection On exterior of enclosure T...

Page 6: ...the connector on the outside of the enclosure There is a proper connection between the clamp and the ve hicle object There are no broken ground connections in the system being protected The panel must...

Page 7: ...13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220 V Rated operational current 5 A 3 A 1 A 0 2 A 0 1 A Minimum contact load 1 mA at AC DC 10 V Fault memory behavior Latch...

Page 8: ...life under rated operating conditions 10 000 switching cycles Contact data acc to IEC 60947 5 1 Utilization category AC 13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220...

Page 9: ...Dimensions GFGC 60 and GFGC 100 enclosure 12 12 12 6 6 12 16 12 12 6 16 6 Ordering Information Load Ampere Rating Mfg Reference No Type Ordering Number 30 A LG30 600 120 3 4 4 PA CH XSLU GFGC 30 B541...

Page 10: ...alid until 05 2019 unless otherwise indicated USA Mexico Exton PA 800 356 4266 610 383 9200 info bender org www benderinc com Canada Mississauga ON 800 243 2438 905 602 9990 info bender ca com www ben...

Reviews: