background image

Ground Fault and Ground Continuity – Protection Panel GFGC

6 GFGC_D00395_00_D_XXEN/05.2019 

Installation troubleshooting tips

•  The ground fault alarm trips instantly on a consistent basis.

   Near-instant tripping may also indicate a serious ground fault in 

the system.

  Ensure that the following items are correct:

 

– The transformer and contactor are wired properly per the 

above wiring diagrams based on the voltage being used.

 

– All phases (including the neutral if one is being used) are going 

through the WN-35BS current transformer. Improper wiring 

can cause an incorrect reading on the ground fault detector.

 

– The ground conductor must not pass through the current 

transformer.

 

– There are no neutral-ground bonds downstream of the de-

vice. Having a neutral-ground bond downstream of the de-

vice will activate the grounded neutral protection alarm.

   The panel must be reset manually via the door-mounted RESET 

button in order to clear the trip.

•  The ground fault alarm trips on a consistent basis, but not 

instantly.

  Ensure all of the above items are correct.
   Ensure there are no ground faults on the system. A non-instant 

trip is an indication that the total leakage current from many 

different sources is adding up to approximately 6 mA. Consult 

the manufacturer for more information and technical support.

•  The open ground alarm trips on a consistent basis.

  Ensure that the following items are correct:

 

– There is a proper pilot wire connection to the connector on 

the outside of the enclosure.

 

– There is a proper connection between the clamp and the ve-

hicle/object.

 

– There are no broken ground connections in the system being 

protected.

   The panel must be reset manually via the door-mounted RESET 

button in order to clear the alarm.

Installation troubleshooting tips (continued)

RCMA421H Ground Fault Monitor

GM420 Ground Continuity Monitor

The RCMA421H is labeled with “

I

Δn

” in the top right corner. 

Possible messages displayed on the screen include:
•  “X mA”: The amount of ground fault current (in mA) read by the 

device.

•  “E 01”: Connection alarm (consult the manufacturer if this alarm 

appears).

•  “E 02”: Connection alarm (consult the manufacturer if this alarm 

appears).

If the RCMA421H has gone into the alarm state, and is not display-

ing an error code, follow these steps to retrieve the mA value:
•  Hold the MENU button for > 1.5 s to enter the main menu.
•  Press the down-arrow button until “HiS” (history) is reached. 

Press the enter/MENU button.

Use this value to assist in determining the source of the ground fault. 

If any error codes appear on the unit, consult the manufacturer for 

more information.

The GM420 is labeled with “Ω LOOP” in the top right corner. 

Possible messages displayed on the screen include:
•  “X Ω”: The resistance of the loop in ohms.
•  “OL”: Overload alarm (open connection).
If the GM420 goes into the alarm state, a reading of “X Ω” generally 

indicates a present, but faulty ground connection. A reading of 

“OL” generally indicates a nonexistant ground connection. Use these 

values to troubleshoot the ground loop connection.
If any error codes appear on the unit, consult the manufacturer for 

more information.

Summary of Contents for B541300044

Page 1: ...GFGC_D00395_00_D_XXEN 05 2019 GFGC Protection Panel Universal Ground Fault and Ground Continuity Panel For 120 VAC to 600 VAC Grounded Systems BENDER Group...

Page 2: ...ance tripping through operation on an inverse time curve per UL943 the standard for personnel protection as well as exceptional noise filtering Open ground detection The internal ground continuity mon...

Page 3: ...ation The green POWER ON lamp illuminates when power is available to the load The red CIRCUIT TRIPPED lamp illuminates when power is removed from the load If unit has tripped clear the fault and press...

Page 4: ...6 7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 208 V Pilot Wire Connection On exterior of enclosur...

Page 5: ...7 H2 Com 120 V 208 V 240 V 277 V 480 V 600 V Incoming Lines Outgoing Lines WN 35BS CT Contactor Control Transformer Always Connected Connect Here 480 V Pilot Wire Connection On exterior of enclosure T...

Page 6: ...the connector on the outside of the enclosure There is a proper connection between the clamp and the ve hicle object There are no broken ground connections in the system being protected The panel must...

Page 7: ...13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220 V Rated operational current 5 A 3 A 1 A 0 2 A 0 1 A Minimum contact load 1 mA at AC DC 10 V Fault memory behavior Latch...

Page 8: ...life under rated operating conditions 10 000 switching cycles Contact data acc to IEC 60947 5 1 Utilization category AC 13 AC 14 DC 12 DC 12 DC 12 Rated operational voltage 230 V 230 V 24 V 110 V 220...

Page 9: ...Dimensions GFGC 60 and GFGC 100 enclosure 12 12 12 6 6 12 16 12 12 6 16 6 Ordering Information Load Ampere Rating Mfg Reference No Type Ordering Number 30 A LG30 600 120 3 4 4 PA CH XSLU GFGC 30 B541...

Page 10: ...alid until 05 2019 unless otherwise indicated USA Mexico Exton PA 800 356 4266 610 383 9200 info bender org www benderinc com Canada Mississauga ON 800 243 2438 905 602 9990 info bender ca com www ben...

Reviews: