Modbus register assignment of the ISOMETER®
49
isoEV425_D00126_09_M_XXEN/03.2019
8.1
ISOMETER® device-specific data type
8.1.1
Device name
The data format of the device name is specified below.
8.1.2
Measured values
Each measured value is available as a channel and consists of 8 bytes (4 regis-
ters). The first measured value register address is 1000. The structure of a
channel is always identical. Content and number depend on the device. The
structure of a channel is shown with the example of channel 1:
Word
0x00
0x01
0x02
0x03
-------------------
0x08
0x09
10 Words in total
Each Word contains two ASCII characters
1000
1001
1002
1003
HiByte
LoByte
HiByte
LoByte
HiByte
LoByte
HiByte
LoByte
Floating point value (Float)
Alarm
type and
test type
(AT&T)
Range
and unit
(R&U)
Channel
description