Technical data
64
isoEV425_D00126_09_M_XXEN/03.2019
Stripping length ....................................................................................................................................................10 mm
Rigid.........................................................................................................................................................0.2…2.5 mm
2
Flexible without ferrules .......................................................................................................................0.75…2.5 mm
2
Flexible with ferrules with plastic sleeve .............................................................................................0.25…2.5 mm
2
Multi-conductor flexible with TWIN ferrules with plastic sleeve..........................................................0.5…1.5 mm
2
Opening force ........................................................................................................................................................... 50 N
Test opening, diameter .......................................................................................................................................2.1 mm
Connection type .................................................................................................................terminals Up, AK1, GND, AK2
Single cables for terminals Up, AK1, GND, AK2:
Cable lengths...................................................................................................................................................... ≤
0.5 m
Connection properties
....................................................................................... ≥
0.75 mm
2
Other
Operating mode ............................................................................................................................Continuous operation
Mounting ..................................................................................................... cooling slots must be ventilated vertically
Distance to adjacent devices from
U
n
> 800 V
............................................................... ≥
30 mm
Degree of protection internal components (DIN EN 60529) .................................................................................. IP30
Degree of protection terminals (DIN EN 60529) ..................................................................................................... IP20
Enclosure material .................................................................................................................................... polycarbonate
DIN rail mounting acc. to................................................................................................................................. IEC 60715
Screw mounting....................................................................................................................2 x M4 with mounting clip
Weight ................................................................................................................................................................≤ 150 g