Data access using the Modbus RTU protocol
41
isoEV425_D00126_09_M_XXEN/03.2019
7.1.2
ISOMETER® answers the Master
7.2
Writing to Modbus registers (parameter setting)
Registers in the device can be modified with the Modbus command 0x10 (set
multiple registers). Parameter registers are available from address 3000. The
content of the register is listed in the table on
.
7.2.1
Master sends a command to the ISOMETER®
In this example, the master addresses the ISOMETER® with address 3 and re-
quests that the content of the register with address 3003 is set to 2.
Byte Name
Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code
0x03
Byte 2
Number of data bytes
0x02
Byte 3, 4
Data
0x0047
Byte 7, 8
CRC16 Checksum
0x81B6
Byte Name Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code
0x10
Byte 2, 3
Start register
0x0BBB
Byte 4, 5
Number of registers
0x0001
Byte 6
Number of data bytes
0x02
Byte 7, 8
Data
0x0002
Byte 9, 10
CRC16 Checksum
0x9F7A