Technical Documentation
KSR-V – Capacitor-Bank Protection Relay
Rev. 05
15
5.5.4 Submenu "setup
relay"
Here, you can configure the output relays. The display shows the following information:
First line selects the relay. Change the setting by using the "
"-key until the tiny arrow on left border
of the display is in the first line and select the relay by pressing "+" or "-". All configurations in the
lines below apply to the selected relay.
Second line allows the inversion of a relay. If the display shows the text "normally open", the relay
will be open if not activated and it will close on activation by an alarm. Accordingly, "normally closed"
refers to inverted behaviour (relay is closed if it is not activated and it will open on activation). If a
certain relay is not assembled in the KSR-V, "not available" will be displayed. To change the setting,
move the arrow on the left side to this line with the "
"-key and use the "
"-key to toggle the setting.
The third line contains selection between "manual reset" (user has to reset the relay manually after
activation) and "automatic reset" (relay resets automatically to inactive state if it is not activated by
an alarm any more). Again, if a certain relay is not assembled in the KSR-V, the text "not available"
will be displayed. To change the setting, move the arrow on the left side to this line with the "
"-key
and use the "
"-key to toggle the setting.