Reference Manual
BLR-CM/BLR-CM3phase
Rev. 08
2018-09
39
Limit switch cycles
100000
1 - 9999999
Cos phi alarm
disabled M, D
disabled, M, DO, D, CP, O, F
Limit cos phi min
c 0.90
c 0.90 – limit max - 0,01
Limit cos phi max
i 0.90
i 0.90 – limit min – 0.01
deltaT (time delay)
300s
1s – 36000s
Harmonic U alarm
M, D
disabled, M, DO, D, CP, O, F
Limit harmonics U
20%
1% - 99,9%
Harmonic I alarm
disabled M, D
disabled, M, DO, D, CP, O, F
Limit harmonics I
50%
1% - 99,9%
Alarm overload P
disable M, D, CP
disabled, M, DO, D, CP, O, F
Limit overload P
1.00kW
1.0 ... 99999.9 kW
Alarm overload Q
disabled M, D
disabled, M, DO, D, CP, O, F
Limit overload Q
1.00kvar
1.0 ... 99999.9 kvar
P-export alarm
disabled CP
disabled, M, DO, D, CP, O, F
Temp1 alarm
DO
disabled, M, DO, D, CP, O, F
Limit temperature 1
25°C
20°C – (temp2)
deltaT (temp. hysteresis) Temp1
1.0°C
0.5°C – 9.9°C
Temp2 alarm
M, D, O
disabled, M, DO, D, CP, O, F
Limit temperature 2
70°C
temp2 – 70°C
deltaT (temp. hysteresis) Temp2
1.0°C
0.5°C – 9.9°C
DI Input alarm
CP
disabled, M, DO, D, CP, O, F
DI trigger
high
high / low
Frequency alarm
disabled
disabled, M, DO, D, CP, O, F
Limit low frequency
45.0Hz
45.0Hz – (limit high -0,1Hz)
Limit high frequency
65.0Hz
(limit low +0,1Hz) – 65.0Hz
Modbus baudrate
9600
1200 – 38400
Modbus parity
8E1
8E1, 8°1, 8N2
Modbus address
1
1 – 247
Storage interval (datalogger)
0 min
0 – 720 min
Synchronisation DI input
off
on / off
Setup DI input
High
High / low