Functions for actuators with specific parameters (Parametrisation with PC-Tool necessary)
Override control and limiting with AC 24 V with relay contacts
Override control and limiting with AC 24 V with rotary switch
a b
e
c d
~
T
Y (DC 0...10 V)
e.g. 1N 4007
1
2
3
5
Y U
a
b
c
Close
1)
MIN
ZS
MAX
d
e
Open
Y
~
T
e.g. 1N 4007
1
2
3
5
Y U
Close
1)
MIN
ZS MAX Open
Y
(DC 0...10 V)
1)
Caution:
This function is only
guaranteed if the start point of the
operating range is defined as min.
0.5 V.
Control open-close
Control 3-point
U
1
2
3
5
Y U
–
+
T
~
1
0
1
0
a
b
~
T
U
e.g. 1N 4007
1
2
3
5
Y U
a
b
Operating controls and indicators
1
0
Adaption
Power
Status
1
4
2
3
5
A
B
1
Direction of rotation switch
Switch over:
Direction of rotation changes
2
Push-button and LED display green
Off:
On:
Press button:
No power supply or malfunction
In operation
Triggers angle of rotation adaptation,
followed by standard mode
3
Push-button and LED display yellow
Off:
On:
Press button:
Standard mode
Adaptation or synchronising process active
No function
4
Gear disengagement button
Press button:
Release button:
Gear disengages, motor stops,
manual override possible
Gear engages, synchronisation starts,
followed by standard mode
5
Service plug
For connecting parameterisation and service tools
Check power supply connection
2
Off and
3
On
Possible wiring error in power supply
GM24G-MF-T
Damper actuator, IP66, parameterisable, Modulating,
AC/DC 24 V, 40 Nm
Functions
www.belimo.eu
GM24G-MF-T • en-gb • 2015-10-16 • subject to changes