Functions with basic values (conventional mode)
Override control with AC 24 V with relay contacts
Override control with AC 24 V with rotary switch
a
b
c
0%
ZS 50%
100%
Y
a
b
c
~
T
Y (DC 0...10 V)
e.g. 1N 4007
1
2
3
5
Y U
~
T
e.g. 1N 4007
1
2
3
5
Y U
0% ZS 50% 100%
Y
(DC 0...10 V)
Remote control 0...100% with
positioner SG..
Minimum limit with positioner SG..
1
2
3
5
Y U
–
+
T
~
SGA24
SGF24
SGE24
Y Z
1 2 3 4
– +
T
~
1
2
3
5
Y U
SGA24
SGF24
SGE24
Y Z
1 2 3 4
Y (DC 0...10 V)
100
0
Y [V]
10
min
0
[%]
–
+
T
~
– +
T
~
Follow-up control (position-dependent)
Position indication
1
3
2
5
– +
T
~
1
3
2
5
Y U
Y U
Y
U
1)
~
T
1
2
3
5
Y U
ZAD24
1 2 3 4
+
–
(1) Adapting the direction of rotation
Control with 4...20 mA via external resistor
Functional check
U
1
3
2
5
4…20
mA
DC 2…10
V
500 Ω
(+)
(–)
U
Y
– +
T
~
Caution:
The operating range must be set to
DC 2...10 V.
The 500 Ω resistor converts the
4...20 mA current signal to a voltage
signal DC 2...10 V
1
3
2
5
– +
T
~
U
Y
Procedure
1. Connect 24V to connections 1
and 2
2. Disconnect connection 3:
– with direction of rotation 0:
Actuator rotates to the left
– with direction of rotation 1:
Actuator rotates to the right
3. Short-circuit connections 2 and 3:
– Actuator runs in opposite direction
GM24G-MF-T
Damper actuator, IP66, parameterisable, Modulating,
AC/DC 24 V, 40 Nm
Functions
www.belimo.eu
GM24G-MF-T • en-gb • 2015-10-16 • subject to changes