Description
Type
Positioner for front-panel mounting, range 0...100%
SGF24
Positioner for wall mounting, range 0...100%
CRP24-B1
Connecting cable 5 m, A+B: RJ12 6/6, To ZTH/ZIP-USB-MP
ZK1-GEN
Connection cable 5 m, A: RJ11 6/4, B: Free wire end, To ZTH/ZIP-
USB-MP
ZK2-GEN
Description
Type
Mechanical accessories
Cable gland, for cable diameter 4-10
Z-KB-PG11
Description
Type
Service Tools
Service Tool, for MF/MP/Modbus/LonWorks actuators and VAV-
Controller
ZTH EU
Belimo PC-Tool, software for adjustments and diagnostics
MFT-P
Adapter to Service-Tool ZTH
MFT-C
Electrical installation
!
Notes
• Connection via safety isolating transformer.
Wiring diagrams
AC/DC 24 V, modulating
Parallel operation
Y
U
1
3
2
5
– +
T
~
DC
(0)2…10
V
DC
2…10
V
1
3
2
5
– +
T
~
Y U
1
1
3
2
5
U
2
1
3
2
5
U
X
Notes
• A maximum of eight actuators can
be connected in parallel.
• Parallel operation is permitted only
on non-connected axes.
• Do not fail to observe performance
data with parallel operation.
Wiring diagram piggyback operation (mechanically coupled
actuators)
1
3
2
5
– +
T
~
Y
1
3
2
5
Master
Slave
Notes
• A maximum of two actuators
can be connected in Master-Slave
operation.
• The Master-Slave operation is
permitted only on one fixed spindle
or on two mechanically coupled
spindles.
• The programming of the Master
actuator is adopted by the Slave
actuator.
GM24G-MF-T
Damper actuator, IP66, parameterisable, Modulating,
AC/DC 24 V, 40 Nm
Accessories
www.belimo.eu
GM24G-MF-T • en-gb • 2015-10-16 • subject to changes