7.2.2 Connection of potential free contact
The
BEKOMAT
®
has a potential-free contact on the power control board. A fault signal can be indicated at a remote
maintenance centre through this.
Illustration
Description / explanation
6 mm (0.23“)
60 mm (2.36“)
1. Prepare the 2/3-wire cable of the potential-free
contact (depending on the application).
If the external TEST button is to be connected
in addition to the potential-free contact,
a 4/5-wire cable must be used for the
connection (depending on the application).
4
J
2
5
6
7
2. Take the dust protection pane
[4]
out.
3. Slide the components of the cable gland
[5, 6, 7]
over
the cable for potential-free contact
[J]
and insert the
cable into the top cover.
Normally Open (NO)
Common (CO)
Normally Closed (NC)
N
PE
L
Neutralleiter (N)
Schutzleiter (PE)
Phase (L)
PE
N
L
4. Connect the cable of the potential-free contact to the
power control board in accordance with the terminal
diagram.
Original installation and operation manual
BEKOMAT
®
13, 13 CO, 13 CO PN25, 13 CO PN40
31 | 64